NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (800 mm Width)
2 Product Description
Issue 05 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
23
Table 2-6
Optional specifications for the standard indoor unit
Item
NetCol8000-A013U40E0
NetCol8000-A013U4WE0
Power
specifications
380–415 V AC, 50 Hz or 60 Hz 3Ph
Voltage tolerance: –15% to 10%; frequency tolerance: ±3 Hz
Power supply
mode
Single power supply
Single power supply
Heating
function
No
Yes
Humidification
function
No
Yes
Reheating
capacity
-
4 kW
Humidifying
capacity
-
3 kg/h
Table 2-7
Standard Outdoor unit specifications
Item
NetCol500-A022
Power specifications
220–240 V AC, 50 Hz or 60 Hz 1Ph
Voltage tolerance: –15% to 10%; frequency tolerance: ±3
Hz
Max Current
30 A
Number of fans
2
Net/Gross weight
117 kg/135 kg
Protection level
IPX4
Environment class
Class B
Altitude
0–4000 m, derating at above 1000 m
Certification
CQC, CE, CCC, RoHS, REACH, WEEE, SASO
Outdoor unit installation environments are classified as follows based on the harshness:
Class A (controlled environment): indoor environments where temperature and humidity
are controlled, including rooms where people live.
Class B (uncontrollable environment): indoor environments where the ambient
temperature and humidity are not controlled or general outdoor environments with
simple shielding measures where the humidity sometimes reaches 100%.