NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (800 mm Width)
5 System Operation and Maintenance
Issue 05 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
111
Figure 5-12
Removing the control board
Step 5
Install a new control board, and tighten the bolts to secure it.
Step 6
Bind cable ties and install cable terminals according to the photo you have taken.
Step 7
Use a Phillips screwdriver to reinstall the left front panel and top cover.
Step 8
Power on the smart cooling product and ensure that it starts properly. Observe it for 30
minutes and ensure that no alarm is generated.
----End
5.4.2.3 Replacing a Module Board
Prerequisites
A module board needs to be replaced.
A spare module board of the same model is available and functional.
Context
Tools: Phillips screwdriver, diagonal pliers, cable tie.
Preparation: Power off the outdoor unit.
Procedure
Step 1
Turn off the indoor unit circuit breaker and circuit breaker in the power distribution cabinet.