NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (800 mm Width)
3 Installation Guide
Issue 05 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
51
Figure 3-31
Connecting a drainpipe
(1) Drainpipe connector:
BSPP 3/4 inch, reserved
port
(2) Rigid pipe conversion adapter:
BSPT 3/4 inch, connected to a rigid pipe
with inner screw threads
(3) Rigid pipe: made
of PP-R or other
material
Procedure
Step 1
Install the rigid pipe conversion adapter to the drainpipe connector.
Step 2
Route the external drainpipe into the cabinet through the side plate or bottom plate. Connect
the external drainpipe to the rigid pipe conversion adapter.
Figure 3-32
Bottom pipe routing