FULLTEST3
EN - 56
Item Description
9
WIRE
touch-screen key to select the material of measured wire (Cu
or Al), coating (PVC, BUTYL RUBBER or EPR/XLPE), section (1,
1.5, 2.5, 4, 6, 10, 16, 25, 35, 50,
70, 95, 120, 150, 185, 240, 300,
400, 500 or 630
mm
2
) and number of conductors (1
y
99). Currently
selected material is displayed on the bottom of the key
10
Measurement result (in green color - result OK, in red color - result
not OK).
11
Real time clock (hh.mm.ss)
12
Unit of the test result (
:
)
13
Measurement result status (symbol
in green color - result OK,
symbol
in red color - result not OK
10. READY message will appear when mains voltage U
L/N
(LOOP L/N) or U
L/PE
(LOOP L/PE) within 100V
y
265V or U
L/L
(LOOP L/L) within 100V
y
460V is
present. Carry out the measurement by pressing the
START/STOP
button
11. Test result (loop impedance) will be displayed in green color equipped with green
symbol and with beep-beep sound if measured/calculated I
SC
corresponds to
entered limit mode and other entered parameters. If measured/calculated I
SC
does not correspond to entered limit mode and other entered parameters the
result will be displayed in red color equipped with red
symbol and with longer
acoustic sound
12. Save the test result by pressing the
SAVE
key (see § 7.1)
CAUTION
x
In case voltage U
L/N
(LOOP L/N measurement) or voltage U
L/PE
(LOOP L/PE measurement) within required range 100V
y
265V is
present at L/N/PE test terminals (also displayed) but there is no
READY message displayed, check if energizing socket is
correctly earthed
x
In case voltage U
L/L
(LOOP L/L measurement) within required
range 100V
y
460V is present at L/N test terminals (also displayed)
but there is no READY message displayed, check if energizing
socket is correctly earthed
x
If limit
mode STD is
selected (result is not evaluated), then the
result will be displayed in white color