FULLTEST3
EN - 35
CAUTION
Before connecting test leads to UUT obligatory assure there is
no external voltage higher than 10V between the test points
where test leads will be connected to, otherwise fuse F4 may
blow
6. Press the
START/STOP
key to perform the measurement. The test result is
shown on the display (see Fig. 31)
Fig. 31 : Visualization of R
PE-4WIRE
test result
Meaning of symbols on the display
Item Description
1
Selected function
2
Progress bar, it follows measurement time during the measurement
(in TIMER mode only)
3
Sub-result – real test current applied
4
Measurement screen touch-screen key
5
LIMIT
touch-screen key to select limit mode (STANDARD, 60204
SET Z or 60204 SET L). Currently selected value (STANDARD
mode) or CALC (60204 SET Z or 60204 SET L mode) is displayed
on the bottom of the key. CALC message means the value is
calculated
6
MODE
touch-screen key to select operation mode (MANUAL or
TIMER). Currently selected mode is displayed on the bottom of the
key.
TIMER mode is available only if STANDARD limit mode is
selected
7
Measurement value (in green color - result
OK
, in red color - result
NON OK
8
Real time clock (hh.mm.ss).
9
Unit of measurement result (
:
)
10
Set measurement time (in TIMER mode only)
11
Measurement result status (symbol
in green color - result OK,
symbol
in red color – result not OK)
7. Test result will currently be displayed in green (result lower than or equal to set
limit value) or in red colour (result higher than set limit value). Final result will be
equipped with green
symbol and with beep-beep sound (result OK) or with red
symbol and with longer beep sound (result not OK) or with yellow
symbol
and with beep-beep sound (result OK, but measurement current was too low)