FULLTEST3
EN - 33
6.2. CONTINUITY OF PE CONDUCTOR – 4-WIRE METHOD (R
PE-4WIRE
)
The continuity measurement performed with the 4-wire method is only available with
a test current of 25A and, due to the nature of the Kelvin method used,
it does not
require any calibration of the test lead resistance
. This means that it is possible to
extend (in pairs) the test cables and perform the test without altering the
measurement result. For the extension of each cable it is recommended to use the
optional
1066-IECN
(Black) and
1066-IECR
(Red)
1. Press the
FUNC
key and select the
RPE-4WIRE
function. The following screen is
shown on the display
Fig. 29 : RPE-4WIRE initial screen
2. Select the test parameters on the instrument (see Table 2) and carry out the
desired setup
Parameter Description
Value
LIMIT
Reference limit threshold
STANDARD
0.01
:
÷ 20.0
:
60204 SET L
60204 SET Z
60204 SET L
Test with 25A current
(see § )
Length: 0.1m ÷ 999.9m
Section: 1, 1.5, 2.5, 4, 6, 10, 16,
25, 35, 50, 70,
95, 120,
150, 185,
240,
300, 400, 500, 630
mm
2
Material: Cu (Copper) or Al
(Aluminum)
60204 SET Z
ZLine: 0.001
:
y
2.000
:
MCB protection: B, C, D, K
Fuse protection: gG, aM
Nominal current protection
(see §)
MODE
Measurement mode
Manual / Timer
TIMER
Measurement time
00:02 ÷ 05:00 (2s ÷ 5min)
Table 2 : Setup parameters of RPE-4WIRE function