FULLTEST3
EN - 8
x
RCD test
¾
AC, A and B type.
¾
General, selective and delayed characteristic.
¾
Voltage range 100 ... 265 V.
¾
Limit contact voltage 25 or 50 V.
¾
I
'
N
= 10, 30, 100, 300, 500, 650 or 1000 mA.
¾
Trip out time at I
'
N
/2 (AC, A and B type).
¾
Trip out time at I
'
N
(AC, A and B type).
¾
Trip out time at 2I
'
N
(AC and A type).
¾
Trip out time at 5I
'
N
(AC and A type) or at 4I
'
N
(B
type).
¾
Ramp test (AC, A and B type).
¾
AUTO test (AC, A and B type).
¾
Visual and acoustic warning in case of exceeded limit
value.
EN61557-6
x
Global earth resistance without RCD’s tripping
¾
Selectable test current with regard to involved RCD.
¾
I
'
N
= 10, 30, 100, 300, 500, 650 or 1000mA.
¾
Measurement with I
'
N
/2 (without tripping out RCD)
¾
Voltage range 100
y
265 V.
¾
Contact voltage U
C
measured during the
measurement.
¾
Limit value (R
A
) fixed to 25 or 50 V/I
'
N
, visual and
acoustic warning in case of exceeded value.
x
Residual voltage
¾
Measurement on power plug (2-wire method).
¾
Measurement on internal components (4-wire
method).
¾
Limit discharge time 1 s or 5 s.
¾
LINEAR or NONLINEAR mode.
¾
Visual and acoustic warning in case of exceeded limit
value.
EN60204-1-§18.5
x
Functional tests (on test socket)
¾
Apparent power P
APP
.
¾
Real power P.
¾
Mains voltage U
L/N
.
¾
Load current I
L
.
¾
Power factor PF.
¾
Leakage current I
PE
(differential method).
¾
Internal phase position exchange.
¾
Limit value (apparent power) adjustable, visual and
acoustic warning in case of exceeded value.
x
AC Current with external clamp (optional)
¾
Measurement in combination with HT96U current
clamp.
¾
Three ranges 1 A, 100 A and 1000 A.
¾
Limit value adjustable, visual and acoustic warning in
case of exceeded value.