Troubleshooting 90
To check the event log for a list of active alarms:
1.
Press the
Enter
button on the front panel display to activate the menu options.
2.
Press the down arrow button until the
Event Log
menu appears.
3.
Press the
Enter
button to display the list of alarms and conditions.
Alarm descriptions and SNMP trap codes
The following table describes power unit alarms and indicates the associated trap codes used by the
Management Module.
Trap code
Alarm name
Alarm description
Alarm type
0
Test trap
This alarm is used for testing traps.
Test trap
1
Charger fault
The charger voltage or current is out of the valid
charger threshold.
Critical
2
Fan fault
A fan is locked or abnormal.
Critical
3
Over temperature 1
The charger temperature exceeded the limit.
Critical
4
Over temperature 2
The D2D temperature exceeded the limit.
Critical
5
Over temperature 3
The inverter temperature exceeded the limit.
Critical
6
Over temperature 4
The bypass SCR temperature exceeded the limit. Critical
7
Over temperature 5
The ambient temperature exceeded the limit.
Critical
8
Over temperature 6
The 1U battery pack cell temperature exceeded the
limit during charging.
Critical
9
Over temperature 7
The 1U battery pack charger temperature
exceeded the limit.
Critical
10
Over temperature 8
The 1U battery pack MOSFET switches temperature
exceeded the limit.
Critical
11
Over temperature 9
The 1U battery pack cell temperature exceeded the
limit during discharging.
Critical
12
DC bus high/low
The DC bus voltage is less than or greater than the
valid temperature.
Critical
13
Soft-start fault
The +/- DC bus voltage cannot be boosted to the
default level.
Critical
14
Bus OVP
The DC bus exceeded the voltage upper threshold. Critical
15
Power DSP fault
The power DSP crashed.
Critical
16
Inverter fault
There is a fault in the inverter circuit.
Critical
17
DC AUX power fault
There is a fault in the DC auxiliary power circuit. Critical
18
AC AUX power fault
There is a fault in the AC auxiliary power circuit. Critical
19
Input volt not OK
The utility voltage is out of the usable voltage range. Critical
20
Input freq not OK
The utility frequency is out of the usable frequency
range.
Critical
21
On battery
The UPS is operating in battery discharging mode. Critical
22
On bypass
The UPS is not powered on and the output is
supplied by utility directly.
Critical
23
Bypass fault
There is a fault in the bypass SCR circuit.
Critical
24
Output fault
There is a fault in the inverter SCR circuit.
Critical
25
Output overload
Load levels are at, or exceeded, the overload
threshold.
Critical
26
Output short
The output is shorted.
Critical
Содержание R12000 XR
Страница 17: ...Overview 17 o Two 3U DirectFlow Battery Packs o Two 1U DirectFlow Battery Packs ...
Страница 98: ...Troubleshooting 98 ...
Страница 99: ...Troubleshooting 99 ...
Страница 100: ...Troubleshooting 100 ...
Страница 101: ...Troubleshooting 101 ...
Страница 102: ...Troubleshooting 102 ...
Страница 103: ...Troubleshooting 103 ...
Страница 104: ...Troubleshooting 104 ...
Страница 105: ...Troubleshooting 105 ...
Страница 106: ...Troubleshooting 106 ...
Страница 107: ...Troubleshooting 107 ...
Страница 108: ...Troubleshooting 108 ...
Страница 109: ...Troubleshooting 109 ...
Страница 110: ...Troubleshooting 110 ...
Страница 111: ...Troubleshooting 111 ...