Maintenance 78
Maintenance
Updating the UPS firmware
Download the HP DirectFlow Upgrade Utility (Upgrade_HP_v00_1b_b11282013.exe) from the HP website
(
http://www.hp.com/go/rackandpower
).
To update the UPS firmware:
1.
From AC mode, move the CAM switch on the power module to the Bypass setting.
2.
Connect a local host computer or device to the power unit serial communications port. For more
information, see either "Connecting the R12000DF serial communications port (on page
50
)" or
"Connecting the R18000DF serial communications port (on page
55
)."
3.
Launch the utility.
4.
Click
Upgrade Now
.
If you receive an error, verify the UPS is in Bypass mode.
During upgrade, the utility:
o
Verifies communication between the power unit and host computer or device
o
Sets the UPS in Bypass mode for the upgrade process
o
Flashes each component individually in order
o
Displays a progress line
5.
From Bypass mode, move the CAM switch on the power module to the AC setting.
Содержание R12000 XR
Страница 17: ...Overview 17 o Two 3U DirectFlow Battery Packs o Two 1U DirectFlow Battery Packs ...
Страница 98: ...Troubleshooting 98 ...
Страница 99: ...Troubleshooting 99 ...
Страница 100: ...Troubleshooting 100 ...
Страница 101: ...Troubleshooting 101 ...
Страница 102: ...Troubleshooting 102 ...
Страница 103: ...Troubleshooting 103 ...
Страница 104: ...Troubleshooting 104 ...
Страница 105: ...Troubleshooting 105 ...
Страница 106: ...Troubleshooting 106 ...
Страница 107: ...Troubleshooting 107 ...
Страница 108: ...Troubleshooting 108 ...
Страница 109: ...Troubleshooting 109 ...
Страница 110: ...Troubleshooting 110 ...
Страница 111: ...Troubleshooting 111 ...