40
Code Error
Condition
Operation Reset Check/Repair
Eb
Condenser
Center
Thermistor
Circuit Open
Condenser temperature
stays below -50°C for 1
second.
Fan control
stays at full
speed.
Press
Reset
Button.
Condenser Center
Thermistor
EC
Low Pressure
Switch Error
While pumping down
refrigeration system, Low
Pressure Switch does not
trip for 6 minutes.
EC blinks.
Press
Reset
Button.
Refrigeration circuit,
Installation
conditions, Line
Valve, Pressure
Switch
EE
Gear Motor
Rotation
Error
During Gear Motor
operation, Rotation Sensor
stays ON for more than 5
seconds or OFF for more
than 20 seconds.
Whole unit
stops.
Press
Reset
Button.
Gear Head locked,
Gear Motor locked,
Rotation Sensor
EL
Spout Error
During Gear Motor
operation, Spout Switch
trips for 2 seconds (count
1), resets but trips again for
2 seconds within 5 minutes
after Gear Motor restarts
(count 2). “EL” appears on
count 1 (floor mounting) or
count 4 (fixed mounting).
Whole unit
stops.
Press
Reset
Button.
Ice Spout clogged,
Spout Switch, Bin
Control Switch
C1
Low Water
Float Switch does not trip at
upper float level for 20
minutes and unit shuts
down. “C1” appears
immediately (floor
mounting) or after 3
repetitions (fixed mounting).
Whole unit
stops.
Press
Reset
Button.
Water supply
interruption, Control
Water Valve not
opening, Flush
Water Valve not
closing, Float
Switch, Water leak
None
Electric Leak
Short Circuit
Electric leak or overcurrent.
Whole unit
stops.
Press
Reset
Button.
Replace
Fuse.
Electric leak, Fuse
Non-Interlock Errors
Code Error
Condition
Operation
Reset
Check/Repair
None
Stuck Float
Switch
During Compressor
operation, Float Switch
stays between upper and
lower float levels for 6
minutes (except for forced
drain or shutdown).
Forced water
supply.
N/A
Float Switch, Water
leak, Dirt in Tank
Содержание TM-500AAE
Страница 4: ...iii 8 FLUSH WATER VALVE 59 9 CONTROLLER BOARD 60 10 LINE VALVE 60...
Страница 7: ...3 2 DIMENSIONS CONNECTIONS...
Страница 13: ...9 2 WIRING DIAGRAM a WIRING DIAGRAM...
Страница 14: ...10 b CONTROL BOX LAYOUT...
Страница 24: ...20 d SEQUENCE 1 Startup Water Supply Floor Mounting...
Страница 25: ...21 1 Startup Water Supply Fixed Mounting...
Страница 26: ...22 2 Startup After completion of water supply Fan Motor and Line Valve start in 2 min Floor Mounting...
Страница 27: ...23 2 Startup After completion of water supply Fan Motor and Line Valve start in 2 min Fixed Mounting...
Страница 28: ...24 3 Startup After Fan Motor and Line Valve start Compressor starts in 15 sec Floor Mounting...
Страница 29: ...25 3 Startup After Fan Motor and Line Valve start Compressor starts in 15 sec Fixed Mounting...
Страница 30: ...26 4 Startup Ice production starts Floor Mounting...
Страница 31: ...27 4 Startup Ice production starts Fixed Mounting...
Страница 32: ...28 5 Normal Operation Bin control and drain cycle 480 sec start Fixed Mounting...
Страница 33: ...29 6 Shutdown After pump down and drain cycle 480 sec start Compressor stops in 5 sec Floor Mounting...
Страница 34: ...30 6 Shutdown After pump down and drain cycle 480 sec start Compressor stops in 5 sec Fixed Mounting...
Страница 35: ...31 7 Shutdown Drain Floor Mounting...
Страница 36: ...32 7 Shutdown Drain Fixed Mounting...
Страница 57: ...53 Fig 1 Fig 2 Fig 3...