5.3.6.5 Image Update & H8 Firmware Update
Patches and error recovery are provided for the individual modules by means of updates.
Both the embedded image and the H8 firmware can only be downloaded to the Board via the
web interface (login as "Master" user required). See also
Chapter 4.4 Firmware Update
The following points should be noted regarding updates:
•
Only experienced users or trained technical personnel should carry
out an update after checking all necessary preconditions.
•
Important:
Faulty updates
or
update attempts
may under certain
circumstances require the Board to be returned to the factory for
rectification at the owner’s expense.
•
Check that the update on hand is suitable for your Board. If in doubt
please consult the support of the
hopf
company.
•
In order to guarantee a correct update, the "
New version of saved
site
" function must be set to "
On each access to the site
" in the
Internet browser used.
•
During the update procedure, the device
must not be switched off
and
settings must not be saved to the flash memory
!
•
Updates are
always
executed as software set. I.e. H8 firmware
image update. Unless specifically defined otherwise in the
SET, it is absolutely essential to complete the H8 firmware update
first, followed by the image update.
•
For the Update please pay attention to the points in
Chapter 4.4
In order to carry out an update, enter the name and the folder in which the update / firmware
image is located in the text field or open the file selection dialogue by pressing the "Browse"
button.
Correct firmware and image designations are (e.g.):
8029NTC_v0100_128.
mot
for the
H8 firmware
(update takes approx. 1-1.5 minutes)
upgrade_8029NTC_v0201.
img
for the
embedded image
(update takes approx. 7-8 minutes)