XNX Universal Transmitter
Installation and Operation
37
3 Transmitters - Distance “d”
Configuration
18 AWG
[1.0 mm2]
16 AWG
[1.5 mm2]
14 AWG
[2.0 mm2]
12 AWG
[3.5 mm2]
XNX mV or EC
With Sensor
190 feet
[58 meters]
300 feet
[91 meters]
480 feet
[146 meters]
770 feet
[234 meters]
XNX IR with
Searchpoint Optima Plus
110 feet
[33 meters]
175 feet
[53 meters]
280 feet
[85 meters]
450 feet
[137 meters]
XNX IR with
Searchline Excel
90 feet
[27 meters]
145 feet
[44 meters]
235 feet
[71 meters]
375 feet
[114 meters]
4 Transmitters - Distance “d”
Configuration
18 AWG
[1.0 mm2]
16 AWG
[1.5 mm2]
14 AWG
[2.0 mm2]
12 AWG
[3.5 mm2]
XNX mV or EC
With Sensor
110 feet
[33 meters]
180 feet
[55 meters]
290 feet
[88 meters]
460 feet
[140 meters]
XNX IR with
Searchpoint Optima Plus
65 feet
[20 meters]
105 feet
[32 meters]
165 feet
[50 meters]
270 feet
[82 meters]
XNX IR with
Searchline Excel
55 feet
[17 meters]
85 feet
[26 meters]
140 feet
[43 meters]
225 feet
[68 meters]
5 Transmitters - Distance “d”
Configuration
18 AWG
[1.0 mm2]
16 AWG
[1.5 mm2]
14 AWG
[2.0 mm2]
12 AWG
[3.5 mm2]
XNX mV or EC
With Sensor
75 feet
[23 meters]
120 feet
[36 meters]
190 feet
[58 meters]
300 feet
[91 meters]
XNX IR with
Searchpoint Optima Plus
45 feet
[13 meters]
70 feet
[21 meters]
110 feet
[33 meters]
180 feet
[55 meters]
XNX IR with
Searchline Excel
35 feet
[11 meters]
55 feet
[17 meters]
90 feet
[27 meters]
150 feet
[46 meters]
2. Several transmitters installed in pairs with each pair
equally spaced from the next pair and the power source.
These distances assume the paired transmitters are
installed within 10 feet [3 meters] of each other.
Power Supply
“d”
“d”
“d”
Transmitters 1 and 2
Transmitters 3 and 4
Transmitters 5 and 6
Figure 32. Transmitters in pairs
2 Transmitters - Distance “d”
Configuration
18 AWG
[1.0 mm2]
16 AWG
[1.5 mm2]
14 AWG
[2.0 mm2]
12 AWG
[3.5 mm2]
XNX mV or EC
With Sensor
485 feet
[147 meters]
775 feet
[235 meters]
1230 feet
[292 meters]
1970 feet
[600 meters]
XNX IR with
Searchpoint Optima Plus
380 feet
[115 meters]
600 feet
[180 meters]
960 feet
[290 meters]
1540 feet
[470 meters]
XNX IR with
Searchline Excel
280 feet
[85 meters]
440 feet
[134 meters]
700 feet
[213 meters]
1130 feet
[344 meters]
4 Transmitters - Distance “d”
Configuration
18 AWG
[1.0 mm2]
16 AWG
[1.5 mm2]
14 AWG
[2.0 mm2]
12 AWG
[3.5 mm2]
XNX mV or EC
With Sensor
190 feet
[58 meters]
300 feet
[91 meters]
480 feet
[146 meters]
770 feet
[234 meters]
XNX IR with
Searchpoint Optima Plus
110 feet
[33 meters]
175 feet
[53 meters]
280 feet
[85 meters]
450 feet
[137 meters]
XNX IR with
Searchline Excel
90 feet
[27 meters]
145 feet
[44 meters]
235 feet
[71 meters]
375 feet
[114 meters]
Содержание XNX-AM Series
Страница 2: ...This page is intentionally left blank ...
Страница 7: ...XNX Universal Transmitter Safety and Information 5 Safety and Information ...
Страница 12: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 10 Introduction ...
Страница 27: ...XNX Universal Transmitter Introduction 25 Menu Navigation ...
Страница 31: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 29 Installation and Operation ...
Страница 102: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 100 Calibration ...
Страница 118: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 116 Maintenance ...
Страница 122: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 120 Warnings and Faults ...
Страница 139: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 137 Specifications ...
Страница 174: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 172 Control Drawings ...
Страница 177: ...XNX Universal Transmitter Control Drawings 175 ...
Страница 179: ...XNX Universal Transmitter Control Drawings 177 Remote Sensor Mount ...
Страница 180: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 178 HART Protocol ...
Страница 193: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 191 Modbus Protocol ...
Страница 200: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 198 Warranty ...
Страница 202: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 200 Index ...
Страница 206: ...This page is intentionally left blank ...