XNX Universal Transmitter
Warnings/Faults
122
Warning
Description
Applicable
Sensors
Latching / Non-Latching
Frequency of Diag-
nostic
Event History Data
Action For Resolution
W009
Sensor 24 VDC
Supply Bad
Optima,
Excel
Non-latching
XNX polls sensor
every 2 seconds,
diagnostic fre-
quency controlled
by sensor
Sensor fault or
warning code
(Note 4)
Check wire of 24V power supply to XNX as well as power supply opera-
tion. Also check wiring between XNX and Optima/Excel.
W010
Sensor Path
Obscured
Optima
Non-latching
XNX polls sensor
every 2 seconds,
diagnostic fre-
quency controlled
by sensor
Sensor fault or
warning code
(Note 4)
Check location for external interference. Check sensor for dirty windows.
Beam Block
Excel
Non-latching
XNX polls sensor
every 2 seconds,
diagnostic fre-
quency controlled
by sensor
Sensor fault or
warning code
(Note 4)
Check location for external interference or obstructions in the IR path.
Check sensor for dirty windows. Check Excel alignment.
W011
Sensor In-
ternal Lamp
Issue
Optima
Latching
XNX polls sensor
every 2 seconds,
diagnostic fre-
quency controlled
by sensor
Sensor fault or
warning code
(Note 4)
Remove and return to Honeywell for repair.
W012
Excessive
Float
Optima,
Excel
Non-latching
XNX polls sensor
every 2 seconds,
diagnostic fre-
quency controlled
by sensor
Sensor fault or
warning code
(Note 4)
Check sensor location for external interference, check sensor for opera-
tion and re-zero where appropriate.
W013
Sensor Loop
Failure, (Sen-
sor is losing/
has lost mA
output signal.
These are
detected by
Optima and
Excel.
Optima,
Excel
Latching
XNX polls sensor
every 2 seconds,
diagnostic fre-
quency controlled
by sensor
Sensor fault or
warning code
(Note 4)
Check that supply voltage is stable. Check wiring between Optima/
Excel and XNX. Check loop impedance of wiring. Check that switches
S3 and S4 are set correctly. If the switch settings need to be changed,
power down the transmitter before changing the switch settings. Once
the problem has been resolved, a Soft Reset must be performed for the
Calibration menu to clear W013.
W014
Sensor Real
Time Clock
issue
Excel
Non-latching
XNX polls sensor
every 2 seconds,
diagnostic con-
trolled by sensor
Sensor fault or
warning code
(Note 4)
Reset “date and time” in Excel, re-cycle Excel power and confirm “date
and time.” If not retained, remove and return to Honeywell for repair.
Содержание XNX-AM Series
Страница 2: ...This page is intentionally left blank ...
Страница 7: ...XNX Universal Transmitter Safety and Information 5 Safety and Information ...
Страница 12: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 10 Introduction ...
Страница 27: ...XNX Universal Transmitter Introduction 25 Menu Navigation ...
Страница 31: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 29 Installation and Operation ...
Страница 102: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 100 Calibration ...
Страница 118: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 116 Maintenance ...
Страница 122: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 120 Warnings and Faults ...
Страница 139: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 137 Specifications ...
Страница 174: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 172 Control Drawings ...
Страница 177: ...XNX Universal Transmitter Control Drawings 175 ...
Страница 179: ...XNX Universal Transmitter Control Drawings 177 Remote Sensor Mount ...
Страница 180: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 178 HART Protocol ...
Страница 193: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 191 Modbus Protocol ...
Страница 200: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 198 Warranty ...
Страница 202: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 200 Index ...
Страница 206: ...This page is intentionally left blank ...