XNX Universal Transmitter
Installation and Operation
40
box in multi-node systems when used with the supplied terminal
jumpers. These jumpers enable an electrical connection without
connecting to the Personality Board. Install them between pins 1
and 2 and between pins 3 and 4 to support multi-node wiring.
Keep the total load resistance for the 4-20mA between 200 and
500
Ω
, including the resistance of the properly selected 4-20mA
cable and input impedance of the equipment to be connected.
Failure to perform ‘Calibrate mA Output’ or with loads outside
the recommended values may result in a diagnostic warning or
fault messages.
If the 20 mA output is not used, a 500 ohm resistor must be
installed.
The transmitter’s power consumption is dependent on the
sensor and options for the specific configuration. For proper
operation, the input voltage must be maintained between 16 and
32 VDC for EC and mV units and between 18 to 32 VDC for IR
units.
Controller
+VE
Signal
-VE
R
L
1
2
3
1-1
1-5
1-3
+V
+mA
-V
XNX
XNX Sink Configuration
Current
Flow
Figure 34. Sink wiring
XNX Source Configuration
Controller
+VE
Signal
-VE
R
L
1
2
3
1-1
1-6
1-3
+V
-mA
-V
XNX
Current
Flow
Terminate cable screen at the detector or controller, not both�
Figure 35. Source wiring
Controller
+V1
+V2
-V2
1-1
1-5
1-6
+V
+mA
-V
XNX
1-3
-mA
-V1
XNX Isolated Configuration
Figure 36. Isolated wiring
Labels applied to the back of the POD identify each of the
connection points.
Note:
Pins 2 and 4 of terminal block TB1 have no internal connection on the
personality board. When used with the terminal block jumpers, pins 2 and 4 can
provide additional 4-20mA connections or supply power for daisy-chained units.
NOTE
!
Содержание XNX-AM Series
Страница 2: ...This page is intentionally left blank ...
Страница 7: ...XNX Universal Transmitter Safety and Information 5 Safety and Information ...
Страница 12: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 10 Introduction ...
Страница 27: ...XNX Universal Transmitter Introduction 25 Menu Navigation ...
Страница 31: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 29 Installation and Operation ...
Страница 102: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 100 Calibration ...
Страница 118: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 116 Maintenance ...
Страница 122: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 120 Warnings and Faults ...
Страница 139: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 137 Specifications ...
Страница 174: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 172 Control Drawings ...
Страница 177: ...XNX Universal Transmitter Control Drawings 175 ...
Страница 179: ...XNX Universal Transmitter Control Drawings 177 Remote Sensor Mount ...
Страница 180: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 178 HART Protocol ...
Страница 193: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 191 Modbus Protocol ...
Страница 200: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 198 Warranty ...
Страница 202: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 200 Index ...
Страница 206: ...This page is intentionally left blank ...