XNX Universal Transmitter
Installation and Operation
56
Options
Local HART Interface
Available with any sensor technology or option, this option
provides an external access to the HART interface in
the transmitter. An intrinsically safe (IS) barrier inside the
transmitter allows the user to attach an external handheld field
communicator for programming and configuration. The external
interface is installed in the lower left cable/conduit port of the
transmitter and is intrinsically safe.
Figure 54. XNX Universal Transmitter with HART interface IS barrier installed
The HART protocol is a communication technology used
with smart process instrumentation, providing two-way
communication simultaneously with the 4-20mA analog signaling
used by traditional instrumentation equipment. For more detailed
information on HART, see the the
.
Implementation of the HART protocol in the transmitter:
•
Meets HART 6.0 physical layer specification
• The physical layer is tested according to HART Physical
Layer Test Procedure, HCF_TEST-2.
• Data transfer rate: 1200 bps.
HART devices can operate in point-to-point or multidrop
configurations.
Caution:
Device address changes must be performed only by qualified service
personnel
CAUTION
!
Point-to-Point Mode
In point-to-point mode, the 4–20 mA signal is used to
communicate one process variable, while additional process
variables, configuration parameters, and other device data are
transferred via HART protocol, as shown in the illustration below.
The 4–20 mA analog signal is not affected by the HART signal.
Control System
or Other Host Application
Multiplexer
Barrier
Handheld Terminal
Field Device
Note:
Instrument power is provided by an interface
or external power source that is not shown.
Figure 55. Point-to-point mode of operation
Содержание XNX-AM Series
Страница 2: ...This page is intentionally left blank ...
Страница 7: ...XNX Universal Transmitter Safety and Information 5 Safety and Information ...
Страница 12: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 10 Introduction ...
Страница 27: ...XNX Universal Transmitter Introduction 25 Menu Navigation ...
Страница 31: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 29 Installation and Operation ...
Страница 102: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 100 Calibration ...
Страница 118: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 116 Maintenance ...
Страница 122: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 120 Warnings and Faults ...
Страница 139: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 137 Specifications ...
Страница 174: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 172 Control Drawings ...
Страница 177: ...XNX Universal Transmitter Control Drawings 175 ...
Страница 179: ...XNX Universal Transmitter Control Drawings 177 Remote Sensor Mount ...
Страница 180: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 178 HART Protocol ...
Страница 193: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 191 Modbus Protocol ...
Страница 200: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 198 Warranty ...
Страница 202: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 200 Index ...
Страница 206: ...This page is intentionally left blank ...