Detectable Gases and Performance
Gas detection performance is dependent upon temperature and humidity. The data in this table is based on 68°F (20°C) and 50% relative
humidity. Response times are longer when operating in colder temperatures.
Gas
Selectable Full
Scale Range
Default
Range
Steps
Selectable Cal
Gas Range
Default
Cal Point
Response Time
(T90) secs
Accuracy (ppm or
% of applied gas)
Drift over
time
Operating Temperature
1
Min
Max
Oxygen
25.0% / Vol only
25.0% Vol
n/a
20.9%/Vol (Fixed) 20.9% / Vol
15
+/-0.5% O2
<4% / yr
-40°F (-40°C)
131°F (55°C)
Hydrogen Sulfide
10.0 to 50.0 ppm
15.0 ppm
0.1 ppm
30 to 70% of
selected full scale
range
10 ppm
30
+/-0.3 or +/-20%
<0.5 ppm/yr
-40°F (-40°C)
131°F (55°C)
Hydrogen Sulfide
50 to 500 ppm
100 ppm
10 ppm
50 ppm
30
+/-2 or +/-20%
<0.5 ppm/yr
-4°F (-20°C)
131°F (55°C)
Carbon Monoxide
100 to 1,000 ppm
300 ppm
100 ppm
100 ppm
30
+/-2 or +/-20%
<2 ppm/yr
-40°F (-40°C)
131°F (55°C)
Sulfur Dioxide
5.0 to 20.0 ppm
15.0 ppm
5.0 ppm
5.0 ppm
40
+/-0.3 or +/-20%
<2% / mo
-40°F (-40°C)
131°F (55°C)
Ammonia
50 to 200 ppm
200 ppm
50 ppm
100 ppm
180
+/-10 or +/-20%
<5% / 6 mo
-4°F (-20°C)
122°F (50°C)
2
Ammonia
200 to 1,000 ppm 1,000 ppm 50 ppm
300 ppm
180
+/-15 or +/-20%
<5% / 6 mo
-4°F (-20°C)
104°F (40°C)
Chlorine
5.0 to 20.0 ppm
5.0 ppm
5.0 ppm
2.0 ppm
90
+/-0.3 or +/-20%
<2 ppm / yr
14°F (-10°C)
131°F (55°C)
Chlorine Dioxide
1.00 ppm only
1.00 ppm
n/a
0.5 ppm
120
+/-30%
<5% / yr
-4°F (-20°C)
131°F (55°C)
Nitric Oxide
100 ppm only
100 ppm
n/a
50 ppm
50
+/-3 or +/-20%
<2% / mo
-4°F (-20°C)
131°F (55°C)
Nitrogen Dioxide
5.0 to 50.0 ppm
10 ppm
5.0 ppm
5 ppm
60
+/-3 or +/-20%
<2% / mo
-4°F (-20°C)
131°F (55°C)
Hydrogen
1,000 ppm only
1,000 ppm
n/a
500 ppm
90
+/-10 or +/-25%
<2% / mo
-4°F (-20°C)
131°F (55°C)
Hydrogen
9,999 ppm only
9,999 ppm
n/a
5000 ppm
90
+/-25 or +/-30%
<10% / 6 mo
-4°F (-20°C)
131°F (55°C)
Hydrogen Chloride
10.0 to 20.0 ppm
10 ppm
1.0 ppm
5.0 ppm
180
+/-3 or +/-20%
<20% / yr
-4°F (-20°C)
131°F (55°C)
Hydrogen Fluoride
10.0 to 12.0 ppm
12.0 ppm
0.1 ppm
5.0 ppm
300
+/-30%
<20% / yr
-4°F (-20°C)
131°F (55°C)
Phosphine
1.2 ppm only
1.2 ppm
n/a
0.5 ppm
33
+/-0.03 or +/-20%
<10% / yr
-4°F (-20°C)
131°F (55°C)
Hydrogen cyanide
30.0 ppm only
30.0 ppm
n/a
10.0 ppm
<200
<±0.4 ppm
<2% / mo
-4°F (-20°C)
131°F (55°C)
Fluorine
4 ppm only
4.00 ppm
n/a
2.0 ppm
<30
<±0.03 ppm
<2 ppm / yr
-4°F (-20°C)
131°F (55°C)
Ozone
0.400 ppm only
0.400 ppm
n/a
0.200 ppm
<60
3
<±0.003 ppm
<5% / mo
-4°F (-20°C)
131°F (55°C)
EtO
20.0 to 50.0 ppm
25.0 ppm
5.0 ppm
10.0 ppm
<125
3
<±0.3 ppm
< 5% / yr
-4°F (-20°C)
131°F (55°C)
1 When operating in Hazardous Area applications the detector must not be operated outside the certified temperature range. See Certification details for UL and ATEX/IECEx certified temperature ranges.
2 +131F/+55C intermittent
3 Data from temperature test
Содержание XNX-AM Series
Страница 2: ...This page is intentionally left blank ...
Страница 7: ...XNX Universal Transmitter Safety and Information 5 Safety and Information ...
Страница 12: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 10 Introduction ...
Страница 27: ...XNX Universal Transmitter Introduction 25 Menu Navigation ...
Страница 31: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 29 Installation and Operation ...
Страница 102: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 100 Calibration ...
Страница 118: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 116 Maintenance ...
Страница 122: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 120 Warnings and Faults ...
Страница 139: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 137 Specifications ...
Страница 174: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 172 Control Drawings ...
Страница 177: ...XNX Universal Transmitter Control Drawings 175 ...
Страница 179: ...XNX Universal Transmitter Control Drawings 177 Remote Sensor Mount ...
Страница 180: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 178 HART Protocol ...
Страница 193: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 191 Modbus Protocol ...
Страница 200: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 198 Warranty ...
Страница 202: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 200 Index ...
Страница 206: ...This page is intentionally left blank ...