XNX Universal Transmitter
Specifications
142
EC Sensor Performance Data, Factory Mutual Verified
Certifications by Part Number Series
)
Gas
Cartridge
Part Number
Selectable Full
Scale Range (Dis-
play and 4-20mA
Full Scale)
Default
Range
Range
Incre-
ments
Lower
Alarm
Limit
Lower
Detection
Limit
Lower
Explosive
Limit
(% Vol)
Zero
Deviation
Selectable
Cal Gas
Range
Default
Cal Point
Response
Time T50
(sec)
Response
Time T90
(sec)
Accuracy
Operating Temperature Operating Humidity EC Sensor
Expected
LIfe
(months)
Min
Max
Min
Max
O
2
Oxygen
XNXXSO1FM
n/a
23.0% Vol
n/a
5.0%Vol
5% Vol
n/a
n/a
20.9 %Vol
(fixed)
20.9 %Vol T20 <10
<30
<+/-0.5 %Vol
-30°C / -34°F 55°C /131°F
15% RH
90% RH
24
H
2
S
Hydrogen Sulfide
XNXXSH1FM
10.0 to 50.0 ppm
15.0 ppm 0.1 ppm 5.0 ppm
1.5 ppm
n/a
-2.5 ppm
30 to 70%
of the
selected full
scale range
10 ppm
<20
<30
2 ppm or 10% of
reading, whichever
is greater
-40°C / -40°F 55°C / 131°F
15% RH
90% RH
12
CO
Carbon Monoxide
XNXXSC1FM1
100 to 1000 ppm
300 ppm 100 ppm 30 ppm
15 ppm
na/
-25 ppm
100 ppm
<15
<30
See footnote 1 -40°C / -40°F 55°C / 131°F
15% RH
90% RH
TBD
Footnotes:
1.
XNXXSC1FM accuracy over temperature <±10% of reading 20°C/68°F to 55°C/131°F, <±20% of reading 20°C/68°F to -10°C/14°F, <±30% of reading -10°C/14F to -20°C/-4°F.
Recalibration is recommended if the temperature of the local environment has varied by more than -30°C.
Notes:
•
Performance figures are measured by test units calibrated at 50% of full scale, at ambient conditions of 20°C, 50% RH, with the EC weatherproof cover attached
•
IP rating of FM Cartridges is IP63.
• Barometric
pressure effects on the O
2
sensor: The output from the O
2
sensor has pressure effects of <0.1% change of output per % change in pressure. When the barometric
pressure changes by ±20% the output from the O
2
sensor changes <±0.4%Vol. However, the oxygen sensor shows transient behavior when subjected to a rapid change in
ambient pressure due to either weather or altitude. For example, a 10KPa instantaneous positive pressure step change may cause an overscale alarm condition for a period
of about 12 seconds.
•
Operating the EC sensor at extended temperature ranges for a prolonged time period exceeding 12 hours my cause deterioration in the sensor performance and shorten
sensor life. Extended temperature range for XNX EC sensors is -40°C ot -20°C.
•
Response times may increase at lower temperatures.
•
FM performance verification is limited to the requirements of the standards identified in Table 6.3 for each cartridge.
•
Contact Honeywell Analytics for additional data or details.
Содержание XNX-AM Series
Страница 2: ...This page is intentionally left blank ...
Страница 7: ...XNX Universal Transmitter Safety and Information 5 Safety and Information ...
Страница 12: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 10 Introduction ...
Страница 27: ...XNX Universal Transmitter Introduction 25 Menu Navigation ...
Страница 31: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 29 Installation and Operation ...
Страница 102: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 100 Calibration ...
Страница 118: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 116 Maintenance ...
Страница 122: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 120 Warnings and Faults ...
Страница 139: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 137 Specifications ...
Страница 174: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 172 Control Drawings ...
Страница 177: ...XNX Universal Transmitter Control Drawings 175 ...
Страница 179: ...XNX Universal Transmitter Control Drawings 177 Remote Sensor Mount ...
Страница 180: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 178 HART Protocol ...
Страница 193: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 191 Modbus Protocol ...
Страница 200: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 198 Warranty ...
Страница 202: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 200 Index ...
Страница 206: ...This page is intentionally left blank ...