XNX Universal Transmitter
Warnings/Faults
128
Fault
Description
Appli-
cable
Sensors
Latching / Non-
Latching
Frequency of
Diagnostic
Event History Data
Action For Resolution
F119
Cartridge Internal
Electrical Failure
ECC, mV
Non-latching
XNX polls sensor
every 2 seconds,
diagnostic fre-
quency controlled
by sensor
Note 5
Check cartridge connections, check sensor operation, fit replacement
cartridge, replace personality board.
F120
No Sensor
ECC, mV,
Optima,
Excel
Non-latching
2 seconds
Note 2
Indicates a loss of communication with the sensor. Check that the
sensor type indicated in the part number matches the installed hard-
ware. Check the wiring between ECC sensors or Optima/Excel and the
transmitter.
F121
Wrong Cartridge,
error loading sen-
sor parameters
All
Non-latching
At power up and
when cartridge is
changed
0
Contact Honeywell Analytics’ Service Department.
F122
General Diagnos-
tics
Optima,
Excel
Non-latching
XNX polls sensor
every 2 seconds,
diagnostic fre-
quency controlled
by sensor
Sensor fault or warn-
ing code (Note 4)
Check sensor connections, check sensor operation, fit replacement sen
-
sor, replace personalty board.
F123
Sensor Tempera-
ture Error
Optima
Non-latching
Sensor fault or warn-
ing code (Note 4)
Check location for heat sources. Fit with sunshade or other protection.
Change location of the transmitter. Check temperature in Info->Sensor
Status to ensure temperature is being measured properly.
Sensor Tempera-
ture Error
Excel
Non-latching
XNX polls sensor
every 2 seconds,
diagnostic fre-
quency controlled
by sensor
Sensor fault or warn-
ing code (Note 4)
Check location for heat sources. Fit with sunshade or other protection.
Change location of the transmitter. Check temperature in Info->Sensor
Status to ensure temperature is being measured properly.
Sensor Tempera-
ture Error
ECC
Non-latching
2 seconds
Sensor temperature
(Celsius)
Check location for heat sources. Fit with sunshade or other protection.
Change location of XNX. Check temperature in Info->Sensor Status to
ensure temperature is being measured properly.
F125
Calibration Re-
quired
All
Non-latching
2 seconds
Number of days re-
maining until calibra-
tion expires, negative
= number of days
expired
Time since the last span calibration has exceeded a defined limit. Per
-
forming a successful span calibration will clear the condition. The limit is
the maximum calibration interval.
Содержание XNX-AM Series
Страница 2: ...This page is intentionally left blank ...
Страница 7: ...XNX Universal Transmitter Safety and Information 5 Safety and Information ...
Страница 12: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 10 Introduction ...
Страница 27: ...XNX Universal Transmitter Introduction 25 Menu Navigation ...
Страница 31: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 29 Installation and Operation ...
Страница 102: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 100 Calibration ...
Страница 118: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 116 Maintenance ...
Страница 122: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 120 Warnings and Faults ...
Страница 139: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 137 Specifications ...
Страница 174: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 172 Control Drawings ...
Страница 177: ...XNX Universal Transmitter Control Drawings 175 ...
Страница 179: ...XNX Universal Transmitter Control Drawings 177 Remote Sensor Mount ...
Страница 180: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 178 HART Protocol ...
Страница 193: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 191 Modbus Protocol ...
Страница 200: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 198 Warranty ...
Страница 202: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 200 Index ...
Страница 206: ...This page is intentionally left blank ...