Diagnostic and error messages
Video Recorder – User Manual
256
Table 9-4 Error Messages (continued)
Error
Description
User Action
Incorrect Input
coordinates
The Advanced Splitter CV was programmed with
input limits for Output#2 (A2) only, or for Output#1 &
#3 (A1 & A3) only, or for Output#3 (A3) only.
Re-program input limits for
Output#1 only, Outputs #1 & #2,
or Outputs #1, #2, & #3.
Incorrect Number of
Parameters for function
The function was not programmed with the minimum
number of parameters. for example, the Math CV
requires at least 2 inputs to function properly.
Program function with at least the
minimum number of parameters.
Incorrect Output
Coordinates
The Advanced Splitter CV was programmed with
output limits for Output#2 (A2) only, or for Output#1 &
#3 (A1 & A3) only, or for Output#3 (A3) only.
Re-program output limits for
Output#1 only, Outputs #1 & #2,
or Outputs #1, #2, & #3.
Invalid Algorithm Code
Bad algorithm code has been given, bad algorithm
choice. Probably caused by someone incorrectly
editing the configuration file or by a corrupt .LNC file.
Verify programming of affected
function block.
Invalid Block Number
Probably caused by someone incorrectly editing the
configuration file or by a corrupt .LNC file.
Verify programming of affected
function block.
Invalid Block Type
Probably caused by someone incorrectly editing the
configuration file or by a corrupt .LNC file.
Verify programming of affected
function block.
Invalid Channel in Point
spec
Invalid channel has been found.
Verify programming of affected
function block.
Invalid Equation
Free form math equation is invalid.
Check equation.
Invalid Function Block
Request
Probably caused by someone incorrectly editing the
configuration file or by a corrupt .LNC file.
Verify programming of affected
function block.
Invalid Index code
Probably caused by someone incorrectly editing the
configuration file or by a corrupt .LNC file.
Verify programming of affected
function block.
Invalid Input Connection
Function block is programmed with wrong input type.
Probably caused by someone incorrectly editing the
configuration file or by a corrupt .LNC file.
Verify programming of affected
function block.
Invalid Machine Update
Rate
Bad machine scan rate.
Re-enter machine scan rate.
Invalid Parameter Code
Bad parameter code has been found. Generally
caused by transferring configurations between
instruments with different software versions.
Verify programming of affected
function block.
Invalid Parameter for
Data Type
Probably caused by someone incorrectly editing the
configuration file or by a corrupt .LNC file.
Verify programming of affected
function block.
Invalid Tag
Probably caused by someone incorrectly editing the
configuration file or by a corrupt .LNC file.
Verify programming of affected
function block.
Invalid Tag Request
Probably caused by someone incorrectly editing the
configuration file or by a corrupt .LNC file.
Verify programming of affected
function block.
Invalid Type in Point
Spec
A class of block was detected that is invalid for the
product.
Verify programming of affected
function block.
Lag or Delay Less than
Zero
AI lag or delay is less than zero.
Change lag or delay to greater
than or equal to zero.
Содержание VRX180
Страница 1: ...Issue 3 03 03 US1I 6228 Video Recorder VRX180 User Manual ...
Страница 2: ...Issue 3 03 03 US1I 6228 ...
Страница 6: ...iv Video Recorder User Manual ...
Страница 48: ...Installation Video Recorder User Manual 34 ...
Страница 222: ...Setpoint Profiler Video Recorder User Manual 208 ...
Страница 234: ...Online Operations Using Primary Displays Video Recorder User Manual 220 ...
Страница 278: ...Appendix A Video Recorder User Manual 264 ...
Страница 290: ...Safety Video Recorder User Manual 276 ...