Online Operation Using Menus
Video Recorder – User Manual
238
Pretune Loop
Pretune calculates optimum values for a loop's Proportional Band/Gain, Reset and Rate by analyzing
the reaction of the loop to a "step change" in setpoint or output. After these new tuning values have
been calculated you have the option of applying (installing) or not applying them to a preselected tune
set of the loop. You can pretune a loop while another loop is pretuning.
To use pretune, your process time constant must be at least 60 seconds. The
process time constant
is
defined as the time needed for the PV to change by 63% of a step change in the setpoint. For example,
if the setpoint changes instantaneously by 100 degrees, the time constant is the amount of time needed
for the PV to change 63 degrees.
To pretune a loop, select PRETUNE from the TUNE LOOP online menu. Select a loop to tune. Pretune
occurs in 4 stages as indicated by the status. Each status has its own menu. Table 7-10 shows the
stages of pretune.
Table 7-10 Stages Of Pretune
Order
Status
Meaning
1
STOPPED
Pretuning not operating, waiting to be started by operator. See STOPPED menu.
2
IDENTIFYING
Pretune is identifying process dynamics as a result of a setpoint or output change.
This process may take up to 4 to 6 process time constants. See Table 7-12
3
CALCULATING
Identification is complete and calculation of new tuning parameters is in process.
See Table 7-12
4
COMPLETE
Calculations are complete and new parameters are ready to replace the loop's
tuning parameters, if desired. See Table 7-13
NOTE:
While using Pretune, it is recommended that Overshoot Suppression is turned off. With
overshoot suppression on, Pretune may not work or may give inaccurate tunings.
Pretune STOPPED menu
Table 7-11 describes the Pretune STOPPED prompts.
Table 7-11 Pretune STOPPED Prompts
Prompt
Range/Selections
Definition
STATUS
This is a read-only prompt.
Status stopped.
PV
This is a read-only prompt.
Current process variable value of the loop being tuned.
OUTPUT
This is a read-only prompt.
Current output value of the loop being tuned.
SETPOINT
This is a read-only prompt.
Current working set point value of the loop being tuned
TUNE SET
Select which set of tuning
parameters (#1 or #2) will
be pretuned and installed.
If tuning a split loop, set#1 applies to loop output between 0
and +100; set#2 applies to loop output between 0 and -100.
OPTIMIZE
Select SET PT or LOAD
This optimizes the new tuning parameters according to their
intended use (that is, controlling changes in setpoint or
process load).
OVERSHOOT
Select YES or NO.
This determines whether or not some overshoot is
acceptable in the pretune specified tuning.
Continued on next page
Содержание VRX180
Страница 1: ...Issue 3 03 03 US1I 6228 Video Recorder VRX180 User Manual ...
Страница 2: ...Issue 3 03 03 US1I 6228 ...
Страница 6: ...iv Video Recorder User Manual ...
Страница 48: ...Installation Video Recorder User Manual 34 ...
Страница 222: ...Setpoint Profiler Video Recorder User Manual 208 ...
Страница 234: ...Online Operations Using Primary Displays Video Recorder User Manual 220 ...
Страница 278: ...Appendix A Video Recorder User Manual 264 ...
Страница 290: ...Safety Video Recorder User Manual 276 ...