Model SK-5208 Fire Control/Communicator Installation and Operation Manual
3-12
P/N 151204
Notification Appliance
Circuit 4
34
+
NAC4
3 Amp maximum per circuit. Voltage 27.4 VDC, 1.5
Ohms Maximum.
Note:
Total control panel current is 6 Amps.
35
_
Notification Appliance
Circuit 3
36
+
NAC3
37
_
Notification Appliance
Circuit 2
38
+
NAC2
39
_
Notification Appliance
Circuit 1
40
+
NAC1
41
_
Auxiliary Relay 4
42
NO
Relay contacts are rated at 2.5 A, 24 VDC/24VAC
(inductive rating). 5A, 24 VDC/24 VAC (resistive).
Connect to power limited source only.
43
COM
44
NC
Auxiliary Relay 3
45
NO
46
COM
47
NC
Auxiliary Relay 2
48
NO
49
COM
50
NC
Auxiliary Relay 1
51
NO
52
COM
53
NC
Telco Line 2
54
TIP
P2
Telephone line 2 connection terminals (see Section 3.10
for wiring diagram).
55
RING
56
TIP
T2
57
RING
Telco Line 1
58
TIP
P1
Telephone line 1 connection terminals (see Section 3.10
for wiring diagram).
59
RING
60
TIP
T1
61
RING
Table 3-4: Terminal Descriptions
Function
Terminal
Number
Terminal Label
Comments
firealarmresources.com
Содержание SILENT KNIGHT SK-5208
Страница 2: ...firealarmresources com ...
Страница 8: ...Installation Manual iv firealarmresources com ...
Страница 9: ...Contents v firealarmresources com ...
Страница 10: ...Installation Manual vi firealarmresources com ...
Страница 17: ...Agency Listings and Requirements P N 151204 2 3 firealarmresources com ...
Страница 118: ...firealarmresources com ...
Страница 120: ...Cut Along the Dotted Line firealarmresources com ...
Страница 121: ...firealarmresources com ...