Model SK-5208 Fire Control/Communicator Installation and Operation Manual
3-22
P/N 151204
3.14.2.2 Wiring the SK-5235
Follow these steps to properly wire the SK-5235 to the control panel.
1. Remove power from the control panel.
2. Wire the SK-5235s as shown in Figure 3-12.
3. Set the ID number. See Table 3-5.
Note: The ID number of 7 is reserved for the built-in touchpad on the SK
-
5208.
4. Reapply power the the control panel.
When the annunciator powers up, it will display its ID code and current status of the panel.
Figure 3-12 Model SK-5235 Connection
Note: Each 5235 touchpad can be individually supervised. See Section 4.2.2 for programming touchpads as
supervised.
ID DIP switches
1
2
3
4
Supervised
Power Limited
Class B
firealarmresources.com
Содержание SILENT KNIGHT SK-5208
Страница 2: ...firealarmresources com ...
Страница 8: ...Installation Manual iv firealarmresources com ...
Страница 9: ...Contents v firealarmresources com ...
Страница 10: ...Installation Manual vi firealarmresources com ...
Страница 17: ...Agency Listings and Requirements P N 151204 2 3 firealarmresources com ...
Страница 118: ...firealarmresources com ...
Страница 120: ...Cut Along the Dotted Line firealarmresources com ...
Страница 121: ...firealarmresources com ...