Model SK-5208 Fire Control/Communicator Installation and Operation Manual
6-4
P/N 151204
6.2.1
Default Settings for 3/1 Format
Table 6-3 displays the default settings which are set in the Misc. Reporting section of
Programming.
Table 6-3: Default Settings for 3/1 Format
Water Alarm Restore 1-30
WH1-WH30
AR1 - AR0
Alarm Restore Code
3 154 001 - 3 154 030
Water Trouble Restore 1-30
WJ1-WJ30
R1 - R0
Restore Code
3 370 001 - 3 370 030
Water Trouble 1-30
WT1-WT30
T1 - T0
Trouble Code
1 370 001 - 1 370 030
Water Unbypass 1-30
WU1-WU30
R1 - R0
Restore Code
3 570 001 - 3 570 030
Communications Failure Line #1
YC1
T1
Trouble Code
1 354 001
Communications Restore Line #1
YK1
R1
Restore Code
3 354 001
Communications Failure Line #2
YC2
T2
Trouble Code
1 354 002
Communications Restore Line #2
YK2
R2
Restore Code
3 354 002
System Battery Restore
YR0
R0
Restore Code
3 302 000
System Battery Trouble
YT0
T0
Trouble Code
1 302 000
Cold Alarm 1-30
ZA1-ZA30
A1 - A0
Alarm Code
1 153 001 - 1 153 030
Cold Bypass 1-30
ZB1-ZB30
T1 - T0
Trouble Code
1 570 001 - 1 570 030
Cold Alarm Restore 1-30
ZH1-ZH30
AR1 - AR0
Alarm Restore Code
3 153 001 - 3 153 030
Cold Trouble Restore 1-30
ZJ1-ZJ30
R1 - R0
Restore Code
2 370 001 - 3 370 030
Cold Trouble 1-30
ZT1-ZT30
T1 - T0
Trouble Code
1 370 001 - 1 370 030
Cold Unbypass 1-30
ZU1-ZU30
R1 - R0
Restore Code
3 570 001 - 3 570 030
Programming
Option
Menu Item
Choices
Default
Comments
Misc Reporting
Test Time
00:00 - 23:59
12:00
Selects the time of day the control will send an
automatic test signal to a central station receiver.
AC Delay
0-30 Hours
2
Selects the delay time (in hours) before the control
will report an AC power loss to the central station.
Report Walk Test
No
No zone information will be reported just test
begin and test end.
By Zone
Test begin, test end, and all events in between will
be reported to central station.
*3/1 Alarm
0 - 9
* Event code for 3/1
and 4/2 reporting
formats.
0
Alarms for Fire, Waterflow, Undefined, Heat,
Cold, and Water events.
*3/1 Alarm Rst
2
Alarms restores for Fire, Waterflow, Undefined,
Heat, Cold, and Water events.
*3/1 Supervisory
6
Sprinkler supervisories.
*3/1 Restore
7
Restore reports for Troubles, Supervisories, and
unbypasses. The only exceptions are the restores
listed as alarm restores.
*3/1 Trouble
8
All system and zone troubles, and zone/NAC
bypasses, and NACs troubles.
*3/1 Test
9
All test events.
Table 6-2: Event and Reporting Code by Format
Event
SIA8 & 20
SK4/2
3/1 1400 &2300
Contact ID
firealarmresources.com
Содержание SILENT KNIGHT SK-5208
Страница 2: ...firealarmresources com ...
Страница 8: ...Installation Manual iv firealarmresources com ...
Страница 9: ...Contents v firealarmresources com ...
Страница 10: ...Installation Manual vi firealarmresources com ...
Страница 17: ...Agency Listings and Requirements P N 151204 2 3 firealarmresources com ...
Страница 118: ...firealarmresources com ...
Страница 120: ...Cut Along the Dotted Line firealarmresources com ...
Страница 121: ...firealarmresources com ...