Model SK-5208 Fire Control/Communicator Installation and Operation Manual
4-10
P/N 151204
4.2.7
Account
Figure 4-9 illustrates, in more detail, the programming flow when in the account menu.
Figure 4-9 Account Programming Menu
Note:
CIC and Phone number can also use special characters as described in Section 4.1.1.
Must
The dialer MUST report events in this family to this account.
Selecting Must makes an account a primary reporting account. The dialer will try to report the event to the primary
account until it exceeds the "Account Tries" value. When the dialer has exceeded the Account Tries retry limit, it will
switch to a backup account (a "Can Report" or "Yes" account, see below). If the dialer cannot report the event to any of the
backup accounts, it will return to the primary account and repeat the process until it exceeds the a total of 10 attempts.
When the Account Tries limit is exceeded, an Account Trouble condition is generated and a local trouble will sound.
Yes
Can Report. Selecting Y makes this a backup account for this event family. The dialer will report to this account only if it
was previously unable to report the event to a Must account.
No
No events in this family will ever be reported to this account.
firealarmresources.com
Содержание SILENT KNIGHT SK-5208
Страница 2: ...firealarmresources com ...
Страница 8: ...Installation Manual iv firealarmresources com ...
Страница 9: ...Contents v firealarmresources com ...
Страница 10: ...Installation Manual vi firealarmresources com ...
Страница 17: ...Agency Listings and Requirements P N 151204 2 3 firealarmresources com ...
Страница 118: ...firealarmresources com ...
Страница 120: ...Cut Along the Dotted Line firealarmresources com ...
Страница 121: ...firealarmresources com ...