Control Panel Installation
P/N 151204
3-11
3.9
Terminal Strip Description
The terminal strips on the PC board are non-removable. Table 3-4 lists the functions of each
terminal. See Section 3.4 for the board layout.
Table 3-4: Terminal Descriptions
Function
Terminal
Number
Terminal Label
Comments
Zone 1 input.
1
A
Z1
Zone 1 input Class A (Style D) or Class B (Style B). See
Section 3.11 for wiring configurations.
2
B
3
C
4
D
Zone 2 input
5
A
Z2
Zone 2 input Class A (Style D) or Class B (Style B). See
Section 3.11 for wiring configurations.
6
B
7
C
8
D
Ground
9
GND
Zone 3 input
10
Z3
Zone input Class B (Style B). Refer to Section 3.11.2.
Power Limited at 100mA. Voltage 27.4 VDC.
Power (Zone 3 & 4)
11
PWR
Zone 4 input
12
Z4
Zone 5 input
13
Z5
Smoke Power
14
PWR
Zone 6 input
15
Z6
Zone 7 input
16
Z7
Smoke Power
17
PWR
Zone 8 input
18
Z8
Zone9 input
19
Z9
Smoke Power
20
PWR
Zone 10 input
21
Z10
Ground
22
GND
AC Power Connections
23
B
24
Earth
25
W
SBUS Connections
26
GND
Used to connect SK-5217 Zone Expanders and 5280
Status Display Modules to the control panel. Accessory
Power (terminals 26 and 27) provides 1 Amp total
current.
27
+24DC
28
A
29
B
Remote Annunciator
Connections
30
SKI
Used to connect 5235 remote annunciators to the control
panel.
31
SKO
32
PWR
33
GND
firealarmresources.com
Содержание SILENT KNIGHT SK-5208
Страница 2: ...firealarmresources com ...
Страница 8: ...Installation Manual iv firealarmresources com ...
Страница 9: ...Contents v firealarmresources com ...
Страница 10: ...Installation Manual vi firealarmresources com ...
Страница 17: ...Agency Listings and Requirements P N 151204 2 3 firealarmresources com ...
Страница 118: ...firealarmresources com ...
Страница 120: ...Cut Along the Dotted Line firealarmresources com ...
Страница 121: ...firealarmresources com ...