Model SK-5208 Fire Control/Communicator Installation and Operation Manual
3-32
P/N 151204
Mounting the SK-5217 into the SK-2190 Accessory Cabinet.
Follow these steps to properly mount the SK-5217 zone expander into the SK-2190 cabinet:
1. Mount the remote cabinet using the cabinet mounting holes. See Figure 3-23.
Refer to Section 3.5 for proper cabinet mounting procedures.
2. Remove power from the control panel.
3. Mount the SK-5217 onto the standoffs and bracket located in the cabinet. See Figure 3-23.
Figure 3-23 Model SK-5217 Remote Installation
4. Connect the SK-5217 to the SK-5208 control panel as shown in Figure 3-19.
5. Set the ID code (see Section 3.14.1).
If ID code 1 is selected the SK-5217 will input zones 11 - 20.
If ID code 2 is selected the SK-5217 will input zones 21 - 30.
6. Wire the zone inputs to the zone expander as shown in Figure 3-20.
Mounting
Holes
Mounting
Holes
firealarmresources.com