On-board Touchpad and SK-5235 Operation
Basic operations for the on-board annunciator (touchpad) and SK-5235 are described in Table
5-1. If you are using an annunciator key or the Flex Door option, you are not required to enter
a code for operator level functions.
If no keys are pressed for 4 minutes while in program mode, the system will time out and
resume normal operation.
* Code = any valid operator or installer code.
Table 5-1: Basic Panel Operations Using the On-Board Annunciator and the SK-5235
How To
Do This
Comments
Press
Display
Message
Press*
Test the system
System Test
Enter Code
Enter Code
System performs a display lamp test, a
communication test, and displays the firmware
number and revision. See 5.2.1 for an example.
Reset Alarms
or
Reset Alarm
Enter Code
Enter Code
Resets system.
Clear History
Clear History
Enter Code
Enter Installer
Code
Clears event history of all events.
Reset the Dialer
Reset Dialer
Enter Code
Enter Code
Resets the dialer and aborts the call to central
station.
Call Computer to Up/
Download
Call Computer
Enter Code
Enter Installer
Code
Will dial the programmed phone number for the
computer to initiate an up or download.
Display History
Events
History Events
Enter Code
Enter Code
Displays panel history, including alarms,
supervisories, troubles, reports, time and date
changes, etc.
Show Status
Show Status
Enter Code
Enter Code
View existing system status. List Alarms first,
supervisories and then troubles.
Silence Troubles or
Alarms
or
Silence
Enter Code
Enter Code
Set the Date
Set Date
Enter Code
Enter Code
Enter 8 digits for the date. For example, to set
the date 08/31/1999 enter 08311999. Press
to clear incorrect entries.
Set the Time
Set Time
Enter Code
Enter Code
Enter the time in 24 hour increments. For
example, 1:00 pm = 13:00.
Disable/Enable a
Zone
Zone # +
Disable Zone
Enter Code
Enter Code
Repeat the process to enable the zone.
Disable/Enable NAC
NAC #
Disable NAC
Enter Code
Enter Code
Repeat the process to enable the NAC.
Conduct a Fire Drill
Fire Drill
Enter Code
Enter Code
To End the Fire Drill press
then code.
Reset Detectors
Rst Smk Pwr
Enter Code
Enter Code
Resets all smoke detector power.
Walk Test the System
Walk Test
Enter Code
Enter Code
To End the Walk Test press
.
Menu of Options
Press
or
to
scroll through list.
To exit press
or wait 15 seconds.
0
1
2
3
4
5
6
7
8
#
9
1
0
2
0
2
1
2
2
firealarmresources.com
Содержание SILENT KNIGHT SK-5208
Страница 2: ...firealarmresources com ...
Страница 8: ...Installation Manual iv firealarmresources com ...
Страница 9: ...Contents v firealarmresources com ...
Страница 10: ...Installation Manual vi firealarmresources com ...
Страница 17: ...Agency Listings and Requirements P N 151204 2 3 firealarmresources com ...
Страница 118: ...firealarmresources com ...
Страница 120: ...Cut Along the Dotted Line firealarmresources com ...
Страница 121: ...firealarmresources com ...