Model SK-5208 Fire Control/Communicator Installation and Operation Manual
4-22
P/N 151204
Line (1-2) #
Options
Line # Dial Type
Not Used
This disables the phone line.
DTMF/USA Rotary
Attempts 1 through 6 will be DTMF, then the
dialer will alternate between Rotary and DTMF for
attempts 7 through 10, Rotary Make/Break ratio is
40/60.
USA Rotary Only
Attempts 1 through 10 will be Rotary only, with a
Make/Break ratio of 40/60.
DTMF Only
Attempts 1 through 10 will be DTMF only.
DTMF/Euro Rotary
Attempts 1 through 6 will be DTMF, then the
dialer will alternate between Rotary and DTMF for
attempts 7 through 10, Rotary Make/Break ratio
33/67.
Euro Rotary Only
Attempts 1 through 10 will be Rotary only, with a
Make/Break ratio of 33/67.
Line # GS
No
Yes enables Ground Start phone functions. A
ground start relay (Model 5211) is required if this
feature is enabled (see Figure 3-2).
Yes
Line # Rings
0 - 15
Line 1: 2
Line 2: 10
Number of rings before the panel will answer an
incoming telephone call.
Line # Ans Mach
No
This feature is used in installations where an
answering machine is on the same phone line that
the control panel is on. The answering machine
may interfere with a computer download.
Yes
When enabled (Yes) the computer calls the control
panel and the phone line rings twice, hangs up and
calls again (within 10 to 60 seconds). When the
control panel see two more rings on the phone line
it will answer and acknowledge the calling
computer.
Line # Prefix
Up to 8 digits
See Section 4.1.1 for special characters.
Misc Reporting
Test Time
00:00 - 23:59
12:00
Selects the time of day the control will send an
automatic test signal to a central station receiver.
AC Delay
0-30 Hours
2
Selects the delay time (in hours) before the control
will report an AC power loss to the central station.
Report Walk Test
No
No zone information will be reported just test
begin and test end.
By Zone
Test begin, test end, and all events in between will
be reported to central station.
*3/1 Alarm
0 - 9
* Event code for 3/1
and 4/2 reporting
formats.
0
Alarms for Fire, Waterflow, Undefined, Heat,
Cold, and Water events.
*3/1 Alarm Rst
2
Alarms restores for Fire, Waterflow, Undefined,
Heat, Cold, and Water events.
*3/1 Supervisory
6
Sprinkler supervisories.
*3/1 Restore
7
Restore reports for Troubles, Supervisories, and
unbypasses. The only exceptions are the restores
listed as alarm restores.
*3/1 Trouble
8
All system and zone troubles, and zone/NAC
bypasses, and NACs troubles.
*3/1 Test
9
All test events.
Table 4-4: Programming Options
Programming
Option
Menu Item
Choices
Default
Comments
firealarmresources.com
Содержание SILENT KNIGHT SK-5208
Страница 2: ...firealarmresources com ...
Страница 8: ...Installation Manual iv firealarmresources com ...
Страница 9: ...Contents v firealarmresources com ...
Страница 10: ...Installation Manual vi firealarmresources com ...
Страница 17: ...Agency Listings and Requirements P N 151204 2 3 firealarmresources com ...
Страница 118: ...firealarmresources com ...
Страница 120: ...Cut Along the Dotted Line firealarmresources com ...
Страница 121: ...firealarmresources com ...