SK-5208 Plus Basic Operating Instructions P/N 151214 Rev. A
These instructions must be framed and displayed next to the panel in accordance with NFPA 72 fire code
for Local Fire Alarm System.
How To
Do This
Comments
Press
Display Message
Press
Test the system
System Test
Enter Code
Enter Code
The system will perform a display lamp test and a
communication test. Displays Firmware Revisions.
Reset Alarms
or
Reset Alarm
Enter Code
Enter Code
Resets system.
Reset the Dialer
Reset Dialer
Enter Code
Enter Code
Resets the dialer and aborts the call to central station.
Display History
Events
History Events
Enter Code
Enter Code
Displays the panel history, which includes alarms,
supervisories, troubles, reports, time and date changes, etc.
Show Status
Show Status
Enter Code
Enter Code
View existing system status. List Alarms first, supervisories
and then troubles.
Silence Troubles or
Alarms
or
Silence
Enter Code
Enter Code
Disable/Enable a Zone Zone # +
Disable Zone
Enter Code
Enter Code
Repeat the process to enable the zone.
Disable/Enable NAC
NAC # +
Disable NAC
Enter Code
Enter Code
Repeat the process to enable the NAC.
Conduct a Fire Drill
Fire Drill
Enter Code
Enter Code
To End the Fire Drill press
then code.
Reset Detectors
Rst Smk Pwr
Enter Code
Enter Code
Resets all smoke detector power.
Walk Test the System
Walk Test
Enter Code
Enter Code
To End the Walk Test press
.
Menu of Options
Press
or
to
scroll through list.
To exit press
or wait 15 seconds.
Acknowledge Events
Events can be acknowledged by pressing the
button. No code is required to acknowledge events. The status LEDs (Alarm,
Supervisory and Trouble) will flash when an un-acknowledged alarm, supervisory, or trouble condition exists.
After each event has been acknowledged its associated LED (Alarm, Supervisory, or Trouble LED) stop flashing and turn on steady.
When viewing system status the LCD displays “Acked” for each individual event once it has been acknowledged. The control panel
piezo will silence after all alarms have been acknowledged.
Note:
The control panel piezo will continue to sound for Supervisories and Troubles even after the event has been acknowledged.
Supervisories and troubles will silence once the event is restored.
After the event is acknowledged an event is added to the event history buffer. Acknowledged events in the history buffer will be preceded
with an asterisk “*”.
LEDs Meaning
LED
Status
Condition
ALARM (red)
Off
Normal condition
On
System in alarm.
Flashing
LED will flash when a alarm condition exists that has not been acknowledged.
SUPERVISORY (yellow)
Off
Normal condition
On
If a supervisory condition exist on the system.
Flashing
LED will flash when a supervisory condition exists that has not been acknowledged.
TROUBLE (yellow)
Off
Normal condition
On
Trouble condition exists
Flashing
LED will flash when a trouble condition exists that has not been acknowledged.
SILENCED (yellow)
Off
Normal condition.
On
Alarm or trouble condition has been silenced but condition still exists.
AC (green)
On
Panel is running on AC (normal condition); standby battery fully charged.
Off
Panel has lost all power.
Flashing
Panel is running on battery power only or AC power only.
0
1
3
5
6
7
1
0
2
0
2
1
2
2
For Service Contact:
firealarmresources.com
Содержание SILENT KNIGHT SK-5208
Страница 2: ...firealarmresources com ...
Страница 8: ...Installation Manual iv firealarmresources com ...
Страница 9: ...Contents v firealarmresources com ...
Страница 10: ...Installation Manual vi firealarmresources com ...
Страница 17: ...Agency Listings and Requirements P N 151204 2 3 firealarmresources com ...
Страница 118: ...firealarmresources com ...
Страница 120: ...Cut Along the Dotted Line firealarmresources com ...
Страница 121: ...firealarmresources com ...