6. PROBLEM SOLVING
Fault/Problem
Causes
Remedies
Diagnostics
Receiver misaligned
1)
Re-align the Receiver, first using the telescope and
report
then using the Interrogator.
Neg Gas
2)
Re-zero the unit.
Reading
Contamination of windows
1)
Check the Transmitter and Receiver windows for build
up of contamination. Clean windows if required. See
Chapter 5
.
2)
Re-zero the unit.
Negative drift of unit’s zero
Re-zero the unit.
position
Diagnostics
Receiver misaligned
1)
Re-align the Receiver, first using the telescope and
report
then using the Interrogator.
Baseline Drift
2)
Re-zero the unit.
Contamination of windows
1)
Check the Transmitter and Receiver windows for build
up of contamination. Clean windows if required.
2)
Re-zero the unit.
Drift of unit’s baseline
Re-zero the unit
Diagnostics
Unit has been operated at a
1)
When Ex certified equipment is operated outside its
report
temperature outside its
certified range, its type approval certification is
Bad
specified
and certified range
invalidated along with its warranty. Such equipment
Temperature
should be removed from service in potentially
explosive atmospheres.
2)
Investigate the cause of the excessive temperature
excursion and take steps to prevent recurrence.
(e.g. fit sunshade or heat-shield, or relocate detector,
etc.)
Diagnostics
Incorrect supply voltage
1)
Check that the +24V supply voltage reaching the unit
report
reaching unit
(it should be b18V and +32V).
Supply Fault
2)
Identify the cause of incorrect supply voltage reaching
the unit and rectify.
Diagnostics
Fault on the unit's digital
If this fault is displayed when the unit is interrogated, it cannot
report
PCB
be remedied in the field.
DSP Fault
Diagnostics
A fault has been detected in
If this fault is displayed when the unit is interrogated, it cannot
report
the NV-RAM
be remedied in the field.
NV-RAM Fault
Diagnostics
The time and date record
1)
Re-enter the time and date using the Interrogator.
report
being stored by the Real
2)
Cycle the power applied to the unit.
RTC Fault
Time Clock (RTC) has been
3)
Verify that the time and date record was maintained
lost
after cycling the power.
Diagnostics
Voltage reference fault
If this fault is displayed when the unit is interrogated, it cannot
report
detected
be remedied in the field.
Volt Ref Fault
Содержание Searchline Excel Cross-Duct
Страница 1: ...Searchline Excel Infrared Gas Detectors Open Path and Cross duct Technical Handbook ...
Страница 90: ...90 MAN0530 Issue 09 October 03 Searchline Excel 2104M0506 8 CERTIFICATION 8 2 5 System Diagram ...
Страница 93: ...93 MAN0530 Issue 09 October 03 Searchline Excel 2104M0506 8 CERTIFICATION 8 3 3 Certification Label ...
Страница 99: ...99 MAN0530 Issue 09 October 03 Searchline Excel 2104M0506 8 CERTIFICATION ...
Страница 100: ...100 MAN0530 Issue 09 October 03 Searchline Excel 2104M0506 8 CERTIFICATION With DX100 M Termination Unit ...
Страница 124: ......