82
MAN0530 Issue 09 October 03
Searchline Excel
2104M0506
7.1
SYSTEM
OPEN-PATH
CROSS-DUCT
SHORT RANGE
MEDIUM RANGE
LONG RANGE
Available Gases
All: Methane, Ethane, Propane, Butane, Pentane, Hexane,
Ethylene, Propylene, Butadiene, Methanol, Ethanol.
Range
0 - 5 LELm
0 - 5 LELm
0 - 5 LELm
0 - 100%LEL (%LEL/m)
Recommended
Low 1 LELm
Low 1 LELm
Low 1 LELm
Low 20%LEL (%LEL/m)
Alarm Setting
High 3 LELm
High 3 LELm
High 3 LELm
High 50%LEL (%LEL/m)
Minimum Alarm
0.5LELm
0.5LELm
0.5LELm
10%LEL (%LEL/m)
Setting
(greater than 2.5m)
Path Length
5 - 40m
40 - 120m
120 - 200m
Short 0.5 - 2.5m
(15 - 130ft)
(130 - 390ft)
(390 - 650ft)
Long 2.5 - 5.0m
Speed of
T90 less
T90 less
T90 less
T90 less
Response
than 3seconds
than 3seconds
than 3seconds
than 1 second
Output signal
4 — 20mA
4 — 20mA
4 — 20mA
4 — 20mA
Normal operation
Normal operation
Normal operation
Normal operation
(0 — 5LELm)
(0 — 5LELm)
(0 — 5LELm)
(0 — 100%LEL) (0 — 100%LEL/m)
Operating Temp.
All: -40
°
C to +65
°
C (-40
°
F to +150
°
F)
Humidity
All: 0 — 99%RH Non-condensing
Pressure
All: 91.5kPa — 105.5kPa (915 — 1055mBar, non-compensated)
Repeatability
±
0.4LELm
±
0.4LELm
±
0.4LELm
±
10%LEL (%LEL/m)
(<1metre width)
2.5%LEL (%LEL/m)
(1 - 5metre path)
Temperature
±
0.2LEL.m @ zero
±
0.2LEL.m @ zero
±
0.2LEL.m @ zero
±
10%LEL (%LEL/m) @ zero
Drift (-40
°
C to+65
°
C)
±
0.5LEL.m @3LEL.m
±
0.5LEL.m @3LEL.m
±
0.5LEL.m @3LEL.m
±
15%LEL (%LEL/m) @ 60%LEL
Warm-up Time
All: less than 5 minutes (operational), Less than 1 hour (fully stabilised)
Power Supply
All: 18 to 32V
Power Consumption
* Turbo heating activated (below 0
°
C)
No turbo heating
Transmitter
3.5/5* W max
5.5/7.5* W max.
5.5/7.5* W max.
Tx/Rx
total:
Receiver
8W maximum
8W maximum
8W maximum
13W maximum
Enclosure Material
All: 316 Stainless Steel
Weight
Tx/Rx
13kg
Transmitter
3.5kg
7.0kg
7.0kg
Reflector panel
Receiver
3.5kg
3.5kg
3.5kg
1.0kg (short range)
2.5kg (long range)
Vibration
All: 2 — 60Hz, maximum peak to peak amplitude 1mm.
Divergence/
±
0.5
°
±
0.5
°
±
0.5
°
Tx/Rx
±
1.5
°
Misalignment
(~
±
35cm
(~
±
105cm
(~
±
175cm
Retro-tile
±
15
°
Tolerance
at 40m)
at 120m)
at 200m)
(at 5m)
IP rating
All: IP66/67
7. SPECIFICATIONS
Содержание Searchline Excel Cross-Duct
Страница 1: ...Searchline Excel Infrared Gas Detectors Open Path and Cross duct Technical Handbook ...
Страница 90: ...90 MAN0530 Issue 09 October 03 Searchline Excel 2104M0506 8 CERTIFICATION 8 2 5 System Diagram ...
Страница 93: ...93 MAN0530 Issue 09 October 03 Searchline Excel 2104M0506 8 CERTIFICATION 8 3 3 Certification Label ...
Страница 99: ...99 MAN0530 Issue 09 October 03 Searchline Excel 2104M0506 8 CERTIFICATION ...
Страница 100: ...100 MAN0530 Issue 09 October 03 Searchline Excel 2104M0506 8 CERTIFICATION With DX100 M Termination Unit ...
Страница 124: ......