3. INSTALLATION AND OPERATION
The following message is then displayed:
Press Enter to
Release 4-20
(14)
Press
Enter
on the keypad.
The following message is displayed for three seconds:
4-20 Released
The display then changes to show the
Calibrate
menu. The Searchline Excel gas detector
is now
live
.
This completes the final part of the gas detector alignment procedure.
3.7.6 Finishing Up
To finish the alignment process carry out the following procedure:
(1)
Select
Power Off
from the Interrogator
Main
menu
.
(2)
Press
(
Enter
) on the keypad.
Alternatively press the
and
ESC
buttons simultaneously for a fast power off.
Notes:
1.
The SHC1 Handheld Interrogator powers down automatically after five minutes of non-use.
2.
Fast power off and auto power off are disabled when any menu option is selected that
modifies the unit’s configuration.
(3)
Disconnect the Interrogator from the gas detector, reversing the process described at
the beginning of section
3.7.5
.
3.8
SYSTEM CONTROLLER CALIBRATION
This procedure is used to set up the system controller using the Searchline Excel gas detector.
A chosen fixed output signal is sent from the Excel gas detector to the system controller allowing
calibration of the 0 - 100% scale of the controller without having to use gas. The steps use
procedures described in the previous section.
To calibrate the controller carry out the following procedure:
(1)
Connect the Interrogator to the gas detector.
See
Connecting the Interrogator to Searchline Excel Gas Detector
.
(2)
Turn on the Interrogator.
See
Powering Up
.
(3)
Select
Calibrate
from the main menu.
Press the up and down keys on the keypad to navigate through the menu options.
(4)
Press
Enter
on the Interrogator keypad and the
Calibrate
menu is displayed.
(5)
Select
Force 4-20
from the
Calibrate
menu.
Содержание Searchline Excel Cross-Duct
Страница 1: ...Searchline Excel Infrared Gas Detectors Open Path and Cross duct Technical Handbook ...
Страница 90: ...90 MAN0530 Issue 09 October 03 Searchline Excel 2104M0506 8 CERTIFICATION 8 2 5 System Diagram ...
Страница 93: ...93 MAN0530 Issue 09 October 03 Searchline Excel 2104M0506 8 CERTIFICATION 8 3 3 Certification Label ...
Страница 99: ...99 MAN0530 Issue 09 October 03 Searchline Excel 2104M0506 8 CERTIFICATION ...
Страница 100: ...100 MAN0530 Issue 09 October 03 Searchline Excel 2104M0506 8 CERTIFICATION With DX100 M Termination Unit ...
Страница 124: ......