119
MAN0530 Issue 09 October 03
Searchline Excel
2104M0506
An open path alarm set at 1 LEL.m would be triggered by any of the situations shown below:
100% 50%
10%LEL
LEL
LEL
1m
2m
10m
LEL.m monitoring is particularly beneficial while the Excel gas detector is protecting the perimeter
of a plant or process, often reducing the quantity of point detectors required. The open path
LEL.m system has the ability to detect leaks that point detectors may miss due to prevailing or
changing wind directions, and can provide early warning of a dilute gas cloud when point detectors
may not register any gas presence.
Path Averaged %LEL (%LEL/m)
FM versions of Excel Cross-Duct signal a reading which is the path averaged %LEL (Units of
measure are %LEL/m). This reading is the average %LEL concentration in the duct, based
upon the assumption that the gas concentration in the duct is uniform. Effectively, the reading is
calculated as below:
Path Av %LEL = Number of LEL.m in duct x 100 (%)
Duct Width (m
)
Example
In a
1
metre duct, a
10%LEL/m
reading will be signalled for
1
metre of
10%LEL
gas, or
0.5
metres of
20%LEL
gas, or
0.1
metres of
100%LEL
gas. (This behaviour is similar to that of
conventional open path gas detectors which output readings in
LEL.m
, see previous definition)
Recommended alarm thresholds are
20 %LEL/m
and
40%LEL/
m.
When readings are displayed on the FM version of the SHC1 Handheld Interrogator, the
%LEL/m
unit is displayed as
%L/m
.
B.3 ABBREVIATIONS
CENELEC
European Committee Standardisation
CSA
Canadian Standards Association
DSP
Digital Signal Processor
EMC
Electro-Magnetic Compatibility
APPENDIX B - GLOSSARY
Содержание Searchline Excel Cross-Duct
Страница 1: ...Searchline Excel Infrared Gas Detectors Open Path and Cross duct Technical Handbook ...
Страница 90: ...90 MAN0530 Issue 09 October 03 Searchline Excel 2104M0506 8 CERTIFICATION 8 2 5 System Diagram ...
Страница 93: ...93 MAN0530 Issue 09 October 03 Searchline Excel 2104M0506 8 CERTIFICATION 8 3 3 Certification Label ...
Страница 99: ...99 MAN0530 Issue 09 October 03 Searchline Excel 2104M0506 8 CERTIFICATION ...
Страница 100: ...100 MAN0530 Issue 09 October 03 Searchline Excel 2104M0506 8 CERTIFICATION With DX100 M Termination Unit ...
Страница 124: ......