55
MAN0530 Issue 09 October 03
Searchline Excel
2104M0506
3. INSTALLATION AND OPERATION
Faults/Warning
Enter any
ACTIVE FAULTS
or
ACTIVE WARNINGS
that could not be cleared from the log, e.g.
BEAM BLOCK,
E_ZERO_NOT_CALIBRATED
Installation Satisfactory
Only fully trained personnel trained by Zellweger Analytics or Zellweger Analytics authorised
trainers can declare an installation satisfactory. Mark the
YES
box and sign the form if:
a.
having completed the installation and testing, the unit is operating correctly, and
b.
in the trained installer’s opinion, the unit should continue to operate reliably in this installation/
operating environment providing that nothing significant about the installation/environment is
changed.
If the unit is
not
operating correctly or there are aspects of the installation/operating environment
which in the trained installer’s opinion could or will result in unreliable operation, mark the
NO
box.
Reasons for declaring an installation unsatisfactory could include:
excessive movement/vibration of unit’s mounting,
received signal levels too low,
supply voltage too low,
4 - 20mA loop integrity faults,
unclearable active faults,
any prevailing or probable condition which is known to unacceptably reduce
reliability or availability
If Installation is Unsatisfactory, Reasons
Briefly state the principal reasons why the installation is unsatisfactory, e.g.
Unit mounted on single scaffold pole. Excessive movement,
Beam path obscured by pipes, insufficient received signal levels,
Unit overheated by intense Kuwaiti sunlight
Recommendations
Briefly describe the recommended actions which need to be performed in order to make the
installation satisfactory, e.g.
Mounting pole requires bracing/stiffening,
Pipes obscuring beam to be moved, or detector relocated.
Provide correct supply voltage
Содержание Searchline Excel Cross-Duct
Страница 1: ...Searchline Excel Infrared Gas Detectors Open Path and Cross duct Technical Handbook ...
Страница 90: ...90 MAN0530 Issue 09 October 03 Searchline Excel 2104M0506 8 CERTIFICATION 8 2 5 System Diagram ...
Страница 93: ...93 MAN0530 Issue 09 October 03 Searchline Excel 2104M0506 8 CERTIFICATION 8 3 3 Certification Label ...
Страница 99: ...99 MAN0530 Issue 09 October 03 Searchline Excel 2104M0506 8 CERTIFICATION ...
Страница 100: ...100 MAN0530 Issue 09 October 03 Searchline Excel 2104M0506 8 CERTIFICATION With DX100 M Termination Unit ...
Страница 124: ......