112
MAN0530 Issue 09 October 03
Searchline Excel
2104M0506
The following message is displayed while the calibration operation is being performed:
Processing Data
Please Wait...
If the calibration is successful, the following message is displayed for a period of three seconds:
Zero Calibrated
Force mA
This option allows the system s analogue output signal to be adjusted to a fixed level, e.g. when
setting up a system controller. The following message is displayed:
O/P current mA
mmmmm
where:
mmmmm
Current to output.
This is adjusted using the and
keys over the range 1mA to 21mA in steps of 0.1mA.
After adjustment the output is forced to the set level and the following message is displayed:
Fixed: mmmmm mA
Press Enter
where:
mmmmm
Analogue output current previously set.
Normal mA
This menu option returns the system to its normal analogue output state, irrespective of its
previous state. If successful, the following message is displayed for three seconds:
4-20mA Released
Show Status
This menu option displays the calibration and configuration status of the system. The status
information is displayed in the following format:
cccccccccccccccc
ssssssss
where:
cccccccc...
Title of the calibration status field.
sssssssss
Current state of calibration.
The different settings from the list are selected using the and
keys on the keypad.
APPENDIX A - HANDHELD INTERROGATOR
>
>
Содержание Searchline Excel Cross-Duct
Страница 1: ...Searchline Excel Infrared Gas Detectors Open Path and Cross duct Technical Handbook ...
Страница 90: ...90 MAN0530 Issue 09 October 03 Searchline Excel 2104M0506 8 CERTIFICATION 8 2 5 System Diagram ...
Страница 93: ...93 MAN0530 Issue 09 October 03 Searchline Excel 2104M0506 8 CERTIFICATION 8 3 3 Certification Label ...
Страница 99: ...99 MAN0530 Issue 09 October 03 Searchline Excel 2104M0506 8 CERTIFICATION ...
Страница 100: ...100 MAN0530 Issue 09 October 03 Searchline Excel 2104M0506 8 CERTIFICATION With DX100 M Termination Unit ...
Страница 124: ......