77
MAN0530 Issue 09 October 03
Searchline Excel
2104M0506
The majority of gas detector problems/faults can be diagnosed and corrected using the installation
and alignment kit.
The alignment kit includes:
•
SHC1 Handheld Interrogator
•
alignment telescope
•
set of functional test filters
An electrical multimeter is also useful when diagnosing electrical/wiring problems.
Refer to the troubleshooting tables in this chapter for a list of problems, possible causes and
actions.
Caution: Searchline Excel does not contain any user serviceable parts. Do not open
either the Transmitter or Receiver unit. The warranty of units which have been
opened is invalidated.
NOTE:
THE INFRARED BEAM IS INVISIBLE AND EYE SAFE.
RS485 Modbus signal errors may occur when Excel is connected via a DX100 (M) Termination
Unit and is interrogated/commanded from a network control centre. For troubleshooting these
issues refer to the
DX100 Series Termination Units Technical Handbook
.
If, after following the recommendations in this section, the problem persists, please make available
the following information before contacting Zellweger Analytics:
•
Installation Check Sheet
See
Chapter 3
.
•
Any error message
Displayed on the Handheld Interrogator screen.
•
Any error code
Displayed on the Handheld Interrogator screen.
Fault/Problem
Causes
Remedies
Output is 0mA
Unit is in
FAULT
condition
Connect the SHC1 Interrogator to the unit and use its
DIAGNOSTIC
menu options to ascertain the reason for the
FAULT
report.
Beam block
Check that beam path is clear from the Transmitter to
the Receiver. Remove any obstruction if present.
Transmitter or Receiver
1)
Connect the SHC1 Handheld Interrogator to the
misaligned
unit and check the signal levels.
2)
If signal levels are low, use the telescope and
Interrogator to optimise Receiver alignment.
3)
If signal levels remain low after re-aligning
Receiver, check the Transmitter alignment using
telescope.
4)
Re-zero the unit after alignment. See Appendix A.5.3.4.
6. PROBLEM SOLVING
Содержание Searchline Excel Cross-Duct
Страница 1: ...Searchline Excel Infrared Gas Detectors Open Path and Cross duct Technical Handbook ...
Страница 90: ...90 MAN0530 Issue 09 October 03 Searchline Excel 2104M0506 8 CERTIFICATION 8 2 5 System Diagram ...
Страница 93: ...93 MAN0530 Issue 09 October 03 Searchline Excel 2104M0506 8 CERTIFICATION 8 3 3 Certification Label ...
Страница 99: ...99 MAN0530 Issue 09 October 03 Searchline Excel 2104M0506 8 CERTIFICATION ...
Страница 100: ...100 MAN0530 Issue 09 October 03 Searchline Excel 2104M0506 8 CERTIFICATION With DX100 M Termination Unit ...
Страница 124: ......