6. PROBLEM SOLVING
Fault/Problem
Causes
Remedies
No signal or
Receiver misaligned
Re-align the Receiver, first using the telescope and then using
very low signal
the Interrogator.
at Receiver
Transmitter misaligned
Re-align the Transmitter using the telescope.
The beam path has become
Check that the beam path is clear from Transmitter to
obscured
Receiver.
Remove any obstruction if present.
No output from Transmitter
1)
Check that the Transmitter is flashing. When viewed
on the axis, an orange flash can be seen coming from
the Transmitter.
Alternatively, listen for a distinct ticking sound when the
lamp flashes.
Note: The infrared beam is invisible and eye safe.
2)
If the Transmitter is not flashing, check that the +24V
supply is reaching the Transmitter correctly.
Unit does not
Plastic test filters are only an
Searchline Excel units are calibrated on real gas.
respond exactly approximate simulation of
This results in a variation of the response of different Excel
as expected to
gas
units to plastic test filters. See section 5.1.2.
test filters
1)
Check that the response to the test filters is within the
limits stated in this handbook. See section 5.1.2.
2)
Check that the value being used for response testing
corresponds correctly to the target gas that the unit has
been calibrated for.
Receiver misaligned
1)
Use the telescope and Interrogator to optimise
Receiver alignment.
2)
Re-zero unit.
Contamination of windows
1)
Check the Transmitter and Receiver windows for build
up of contamination. Clean windows if required. See
Chapter 5
.
2)
Re-zero unit.
Drift of unit’s zero position
1)
Verify that there is no gas in the beam path.
2)
Re-zero the unit.
Unit appears to
Misinterpretation of
INHIBIT
,
Searchline Excel does
not
report negative gas readings on
be reporting a
BEAM-BLOCK
or
LOW
the 4-20mA.
negative gas
SIGNAL
currents that are
1)
Configure controller/PLC to interpret and present
reading on the
output on the 4-20mA
currents below 4mA correctly,
4-20mA
or
,
2)
Familiarise operators with the interpretation of sub-
4mA output currents from Excel as follows:
FAULT
0mA
INHIBIT
2mA
BEAM-BLOCK
2.5mA*
LOW SIGNAL
3mA*
or,
3)
Reconfigure the
INHIBIT
,
BEAM-BLOCK
and
LOW
SIGNAL
currents output by the Excel unit.
Содержание Searchline Excel Cross-Duct
Страница 1: ...Searchline Excel Infrared Gas Detectors Open Path and Cross duct Technical Handbook ...
Страница 90: ...90 MAN0530 Issue 09 October 03 Searchline Excel 2104M0506 8 CERTIFICATION 8 2 5 System Diagram ...
Страница 93: ...93 MAN0530 Issue 09 October 03 Searchline Excel 2104M0506 8 CERTIFICATION 8 3 3 Certification Label ...
Страница 99: ...99 MAN0530 Issue 09 October 03 Searchline Excel 2104M0506 8 CERTIFICATION ...
Страница 100: ...100 MAN0530 Issue 09 October 03 Searchline Excel 2104M0506 8 CERTIFICATION With DX100 M Termination Unit ...
Страница 124: ......