Installation and Technical Manual for the
Limitless™ Multi-Protocol Receiver, WMPR Series
ISSUE B
32309669
5.4 | Power Supply Connections
5.4.1 | Description
m
WARNING
The cable length of the customer-supplied dc power source
to the WMPR supply terminals cannot exceed three (3)
meters.
Refer to Figure 2. The Limitless™ WMPR Series has two (2) cage
clamp connectors on the housing’s bottom left. A regulated
voltage supply of 10 Vdc to 30 Vdc needs to be connected to
the power supply terminals identified as “+”
and “-”
. Power
needs to be applied after the EtherNet/IP™ connection has
been made and is active.
,
ATTENTION
Power needs to be applied after the EtherNet/IP™ connection
has been made and is active.
6 | LCD/MENU/MODE OPERATION
6.1 | Start-up or Re-start Sequence Mode
(EtherNet/IP™ Active Connection and
Power Supplied to WMPR)
6.1.1 | Zero Switches or Sensors Paired
to WMPR
Zero switches/sensors paired to the WMPR:
EtherNet/IP™
active connection is made and then applying power to the
WMPR will result in the LCD Menu sequencing through the
following displays before entering the Main Menu.
Figure 4. Honeywell Splash Screen (momentarily
shown)
EtherNet/MAC ID screen appears (see Figure 5). (Record the
MAC ID, IP Address, and then touch the “Next” function button
to move to the Main Menu).
Figure 5. Ethernet/IP ™ MAC ID & IP Address
Figure 6. Main Menu
6.1.2 | One or More Switches or Sensors Paired
to WMPR
One or more switches/sensors paired
to the WMPR: Ether-
Net/IP™ active connection is made and then applying power to
the WMPR will result in the LCD Menu scrolling thru the follow-
ing displays before entering the Main Menu:
Figure 7. Honeywell Splash Screen (momentarily
shown)
System start-up screen (see Figure 8) will take up to two (2)
minutes before displaying EtherNet/IP MAC ID & IP address
(see Figure 9) screen.