18
sensing.honeywell.com
Installation and Technical Manual for the
Limitless™ Multi-Protocol Receiver, WMPR Series
ISSUE B
32309669
Table 20. Pair Mode
Step
Action
1
Completely read this procedure before starting in
order to understand the timing of events that need
to be performed.
2
Limitless™ switch: Remove (if required) the screws
on then housing cover and then the cover of the
Limitless™ switch
and locate the function button
8
(see Figure 3a or b) to be used in Step 4.
Limitless™ analog sensor: Remove (if required) the
screws on the housing cover and then the cover of
the Limitless™ sensor
and locate the function but-
ton
8
(see Figure 3c) to be used in Step 4.
3
WMPR (at PAIR MODE screen): Touch the “Start”
Function button on the WMPR (see Figure 25) at
which time the display will show the following indi-
cating it has entered the pairing mode.
Figure 26. Pairing In Progress
4
Limitless™ switch or analog sensor: Within a 30 sec-
ond interval of Step 3, depress the function button
8
and hold depressed for more than five seconds
but less than 12 seconds at which time the orange
or green
7
LED turns on (see Figure 3a, b, or c).
While in pairing mode, the orange or green led will
flash.
5
WMPR: Successful pairing will be indicated by the
screen displaying the following:
Figure 27. Join Network Notice (switch)
If it is a Analog sensor; wait up to 45s for the indica-
tion that the Node LCD screen has been verified as
indicated by the screen displaying the following:
Figure 28. John Network Notice (analog sensor)
You then must touch the “HOME” function button to
return to the CONFIGURATION MENU.
WMPR: Unsuccessful pairing will be displayed on
the screen as “Node Pairing Failed!” or “Not Paired!”
6
You will need to navigate to the “Node Status” or
“Node Information” menus to confirm proper pairing
between the Limitless™ switch or analog sensor and
WPMR.
7
Repeat Steps 2-7 to add additional Limitless™
switches or analog sensors. Up to 14 Limitless™
switches or analog sensors can be paired to a single
WMPR.