Function Blocks
AMB Auto/Manual Bias Function Block
Revision 11
HC900 Hybrid Control Designer Function Block Reference Guide
69
2/07
Table 22 AMB Alarm tab configuration parameters
Parameter
Index #
Parameter Description
Value or Selection
Alarm 1
Setpoint 1
10
Alarm 1 Setpoint 1 Value
- this is
the value at which you want the
alarm type chose below to activate
–5 % to +105 %
(default 0)
Alarm 1 Type
N/A
Alarm 1 Setpoint 1 Type - select
what you want Alarm 1 Setpoint 1
to represent.
Selections:
NO
ALARM
AL_PV_HI
AL_PV_LO
AL_OUT_HI
AL_OUT_LO
Alarm 1
Setpoint 2
11
Alarm 1 Setpoint 2 Value
Same as
Alarm 1 Setpoint 1
Alarm 1 Type
N/A
Alarm 1 Setpoint 2 Type
Same as
Alarm 1 Setpoint 1
Alarm 2
Setpoint 1
12
Alarm 2 Setpoint 1 Value
Same as
Alarm 1 Setpoint 1
Alarm 2 Type
N/A
Alarm 2 Setpoint 1 Type
Same as
Alarm 1 Setpoint 1
Alarm 2
Setpoint 2
13
Alarm 2 Setpoint 2 Value
Same as
Alarm 1 Setpoint 1
Alarm 2Type
N/A
Alarm 2 Setpoint 2 Type
Same as
Alarm 1 Setpoint 1
Alarm
Hysteresis %
18
Alarm Hysteresis in %
0 % to 5 %