Function Blocks
TPSC (3POS) Function Block
Revision 11
HC900 Hybrid Control Designer Function Block Reference Guide
423
2/07
Table 125 TPSC Motor tab configuration parameters
Properties Group
Parameter
Index #
Parameter Description
Value or Selection
Forward Relay
Output
Rack
Rack Number for Forward
Motor Direction
1 to 5.
Module
49
Module Number for
Forward Motor Direction
1 to 16
Channel
Channel Number for
Forward Motor Direction
Odd number 1 to 15*
Reverse Relay
Output
Rack
Rack Number for
Reverse Motor Direction
1 to 5.
Module
50
Module Number for
Reverse Motor Direction
1 to 16
Channel
Channel Number for
Reverse Motor Direction
Even number 2 to 16*
Motor Data
Deadband
(%)
51
Deadband is an
adjustable gap in which
neither output operates
0.5 % to 5 %
Traverse
Time (sec)
52
Motor Travel Time - the
time it takes the motor to
travel from 0 % to 100 %
0 to 1800 seconds
*For HC900 controller’s 32 Channel DO Module, outputs 17 through 32 may not be used for
TPO (Time Proportioning Output), PPO (Position Proportioning Output) or TPSC (Three
Position Step Output) output types.
Example
H
Figure 116 shows a Function Block Diagram using a TPSC function block.
Figure 116 TPSC function block example