Function Blocks
TPSC (3POS) Function Block
416
HC900 Hybrid Control Designer Function Block Reference Guide
Revision 11
2/07
Table 121 TPSC Range/limit tab configuration parameters
Properties Group
Parameter
Index #
Parameter Description
Value or Selection
Ranging
PV High
Range
3
PV High Range Value
–99999 to 99999
PV Low
Range
4
PV Low Range Value
–99999 to 99999
Display
Decimal
Places
N/A
Number of digits after decimal point
for display
0-5
Units
N/A
Engineering units for display
up to 6 characters
DEV Bar
Range (EU)
N/A
Deviation Bar Range on the
Operator Interface
–99999 to 99999
Limiting
SP High
Limit
18
Setpoint High Limit Value -
prevents the local and remote
setpoints from going above the
value set here.
–99999 to 99999
SP Low
Limit
19
Setpoint Low Limit Value - prevents
the local and remote setpoints from
going below the value set here.
–99999 to 99999
Out High
Limit
33
Autotuning Output High Limit Value
- is the highest value of the output
beyond which the motor no longer
affects the process.
0 % to 100 %
Out Low
Limit
34
Autotuning Output Low Limit Value
- is the lowest value of the output
beyond which the motor no longer
affects the process.
0 % to 100 %
SP Rate
Down
42
Setpoint Rate Down value - when
making a setpoint change, this is
the rate at which setpoint will
change from the original setpoint
down
to the new one.
0 (off) to 9999 (eu/min)
SP Rate Up
43
Setpoint Rate Up value - when
making a setpoint change, this is
the rate at which setpoint will
change from the original setpoint
up
to the new one.
0 (off) to 9999 (eu/min)