Function Blocks
TPSC (3POS) Function Block
Revision 11
HC900 Hybrid Control Designer Function Block Reference Guide
421
2/07
Table 124 TPSC Alarms tab configuration parameters
Properties Group
Parameter
Index #
Parameter Description
Value or Selection
Alarm 1
Setpoint 1
22
Alarm 1 Setpoint 1 Value
- this is the value at which
you want the alarm type
chose below to activate
–99999 to 99999 in Engineering
Units
Within the PV range when alarm
type is PV or SP
Within PV span when alarm type
is DEV
–5 % to 105 % when alarm type is
output.
Type
N/A
Alarm 1 Setpoint 1 Type
-
select what you want
Alarm 1 Setpoint 1 to
represent.
Selections:
NO ALARM
PV_HIGH
High PV Alarm
PV_LOW
Low PV Alarm
DEV_HIGH High
Deviation
alarm
DEV_LOW Low
Deviation
alarm
SP_HIGH
High Setpoint
alarm
SP_LOW Low
Setpoint
alarm
OUT_HIGH High
Output
alarm
OUT_LOW Low
Output
alarm
Setpoint
2
23
Alarm 1 Setpoint 2 Value
Same as
Alarm 1 Setpoint 1
Type
N/A
Alarm 1 Setpoint 2 Type
Same as
Alarm 1 Setpoint 1
Alarm 2
Setpoint 1
24
Alarm 2 Setpoint 1 Value
Same as
Alarm 1 Setpoint 1
Type
N/A
Alarm 2 Setpoint 1 Type
Same as
Alarm 1 Setpoint 1
Setpoint
2
25
Alarm 2 Setpoint 2 Value
Same as
Alarm 1 Setpoint 1
Type
N/A
Alarm 2 Setpoint 2 Type
Same as
Alarm 1 Setpoint 1
Alarm
Hysteresis
%
30
Alarm Hysteresis in %
0 % to 5 %