Function Blocks
AI Function Block
Revision 11
HC900 Hybrid Control Designer Function Block Reference Guide
45
2/07
Failsafe rules
If the controller is unable to access the physical channel or the sensor is faulty, and:
•
If Failsafe is “Use Value”
Then OUT = Configured Failsafe value
•
If Failsafe is enabled and downscale
Then OUT = Range Lo (linear)
Low Range Value of input type (T/C and RTD)
•
If Failsafe is enabled and upscale
Then OUT = Range Hi (linear)
High Range Value of input type (T/C and RTD)