Function Blocks
DC Device Control Function Block
124
HC900 Hybrid Control Designer Function Block Reference Guide
Revision 11
2/07
Block properties
Double click on the function block to access the function block properties dialog box.
Configuration parameters
Table 39 Device control function block parameters
Properties Group
Parameter
Index #
Parameter Description
Value or Selection
Tag Name
N/A
16-character tag name
Display
Descriptor
N/A Block
description
16 characters maximum
On Delay
Time (sec)
1
Starting Time
– time delay
between RUN request and
Output ON.
This parameter is configurable
from the Operator Interface.
Range: 0 – 99999
seconds (default 0)
Settings
Off Delay
Time (sec)
2
Stopping Time – time delay
before the Output turns OFF after
and OFF request.
This parameter is configurable
from the Operator Interface.
Range: 0 – 99999
seconds (default 0)