Function Blocks
PDR Peer Data Read Function Block
260
HC900 Hybrid Control Designer Function Block Reference Guide
Revision 11
2/07
Configuration Parameters
Edit Output Pins
Parameter
Index #
Parameter Description
Value or Selection
Read Signal
N/A
Activates the RD1 through
RD16 pins for reads.
Click on selection box next to the pin
number.
Signal
Number
N/A
Signal Tag number that
appears on the Tag
Information Report.
See "Tag Information
Example".
Enter a tag number from the report.
You can also use the "Find a
Signal tag" procedure to find the
Signal Tag number
.
Use Last
Value
N/A
Use the last known value for
when the associated data
connection is invalid.
Click on selection box for the pin
number.
Failsafe
Value
N/A
Failsafe value for when the
associated data connection
is invalid.
Enter a failsafe value.
Содержание HC900