Function Blocks
RAMP Function Block
314
HC900 Hybrid Control Designer Function Block Reference Guide
Revision 11
2/07
RAMP tabs
It looks like this graphically. There are four ramp tabs, each with the same entry fields. Select the tab for
each ramp at the top of the dialog box.
H
Table 92 describes the parameters and the value or selection for each ramp.
Table 92 RAMP tabs parameters
Properties Group
Parameter
Index #
Parameter Description
Value or Selection
Detail
(for each Ramp #
tab)
Label
N/A
Unique name for each of the 4
internal Ramp functions.
8 Characters
IN
High
Limit
8
through
11
Input HIGH Limit value applied to
the PV after signal lag.
Within the PV range
limits
IN Low Limit
12
through
15
Input LOW Limit value applied to
the PV after signal lag.
Within the PV range
limits
OUT Scale
High Value
0
through
3
High output limit after rescale.
Within the PV range
limits
OUT Scale
Low Value
4
through
7
Low output limit after rescale.
Within the PV range
limits