Function Blocks
AGA8DL Function Block
16
HC900 Hybrid Control Designer Function Block Reference Guide
Revision 11
2/07
AGA8 - Detail tab
Table 4 AGA8DL Detail tab configuration parameters
Properties Group
Parameter
Index #
Parameter Description
Value or Selection
TB
Defines the
Base or
Contract Temperature
to
calculate volume flow rate
at contract conditions in the
units selected by the UNITS
configuration parameter.
ºF for U.S Units
ºC for Metric Units
Contract
Conditions
PB
Defines the
Base or
Contract Pressure
to
calculate volume flow rate
at contract conditions in the
units selected by the UNITS
configuration parameter.
psia for U.S Units
bar for Metric Units
Units U.S
Metric
Type of units for all block
inputs, outputs, and
configuration parameters:
This selection must agree
with the UNITS selection in
the meter block. If they
don’t agree, no error will be
indicated on the error/calc
status pins. The Meter
block will detect the error,
and will alert the user.
Click Radio Button to select.
Ensure that units and gauge
pressure settings are
consistent with the meter
block.