Function Blocks
ON/OFF Function Block
236
HC900 Hybrid Control Designer Function Block Reference Guide
Revision 11
2/07
Table 69 ON/OFF Start/Restart tab configuration parameter
Modes and
Setpoints
Permitted
Mode
MAN 4
AUTO 5
Mode permitted for the
initial start and power up
mode.
Manual
Automatic
May select both, must select one.
Permitted
Setpoint
LSP 6
RSP 7
Setpoint permitted for
the initial start and
power up mode.
Local Setpoint
Remote Setpoint
May select both, must select one.
Initial Mode
N/A
Mode at NEWSTART
Newstart
is the first
scan cycle following the
cold start of the
controller
Manual
Automatic
Select one
Setpoint for
Initial Mode
N/A
Setpoint at NEWSTART
Newstart
is the first
scan cycle following the
cold start of the
controller
Local Setpoint
Remote Setpoint
Select one
Power up
Mode
N/A
Mode at power up
Manual
Retain Last Mode
Same mode (auto or manual)
Select one
Power up
Setpoint
N/A
Setpoint at power up
Local Setpoint
Retain Last LSP/RSP
Same Setpoint (LSP or RSP)
Select one
Power Up
Out
N/A
Output at Power up
LAST OUT
- Same as at power down.
FAILSAFE
- Failsafe output value.
Power Up
Out
Failsafe Out
29
Failsafe Output Value
–5 % to 105 %
Initial
Setpoint
Value
Use initial
LSP
30
Use Initial Local
Setpoint
Click on radio button to select.
Initial LSP
Value
31
Initial Local Setpoint
Value
Enter Initial Local Setpoint Value.