REMEMBER!
To leave the Programming
Mode at any time, press
the
Esc
key. Doing so will
return the CP-220A to its
normal operating mode.
Programming changes will
be stored automatically.
Programming Procedures:
After entering
PARAMETER 60,
[SLOT 1 FORMAT 4x2 WO/P] will be
displayed
.
The number [1] after [SLOT] will be flashing.
If it is necessary to change between these formats as currently specified for
Slot 1, take the following steps:
1. Depress
the key once. The [4x2 WO/P] after [FORMAT] will begin to
flash.
2. Press
the
NEXT
key or the
MANUAL/PREVIOUS
key to display [4x1 W/P]
(4x1 with parity),
which is the alternate selection. Make the desired choice
for
Slot 1.
3. Press
the key so that the [1] after [SLOT] flashes again.
4. To choose between the
4x2 without parity
and the
4x1 with parity
formats, press the number key of the slot desired (e.g.,
2
). The chosen
Slot Number
and its currently assigned
PARAMETER 60
format
selection will be displayed.
5. Repeat the above steps for each
Slot Number
whose format capability
must be changed, in the manner described.
Default:
When it receives a 6-character message, each slot will initially assume its
contents will be in the
4x2 without parity
format (the default)
.
Advancing to Next Parameter:
After programming
PARAMETER 60,
press the
N
key to advance to
PARAMETER 61
– the next parameter in
Category A
.
The CP-220A displays the parameter just programmed ([PARAMETER
NUMBER 60]) with its first digit flashing, indicating its request for the next
parameter number.
You can reach
PARAMETER 61
in one of several ways. Press either:
•
6
then
1
, or
•
then
1
, or
• the
key
NOTE: When the
is used, the
name
of the next parameter appears
immediately – not its
number.
Page 2-56 Section 2: Programming the CP-220A CP-220A Central Station Receiver
Hook-Up and Installation Manual